Trane Precedent RT-PRC005 User Manual page 57

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — 460 Volts — High Efficiency
To Use
Heater
Tons
With
Model No.
BAYHTRR406A
3
THC036A4
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
4
THC048A4
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
5
THC060A4
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS409A
6
THC072A4
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT409A
THC092A4
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT409A
THC102A4
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT418A
10
THC120A4
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
Electrical
Data
Heater
Control
kW Rating
1
Stages
MCA
460 Volts Three Phase
6.0
1
10.4
12.0
2
19.4
17.4
2
27.5
6.0
1
11.1
12.0
2
20.1
17.4
2
28.3
6.0
1
14.7
12.0
2
21.6
17.4
2
29.8
23.0
2
38.3
9.0
1
17.5
18.0
1
30.3
27.0
2
43.8
36.0
2
57.3
9.0
1
19.4
18.0
1
31.0
27.0
2
44.5
36.0
2
58.0
9.0
1
21.4
18.0
1
31.0
27.0
2
44.5
36.0
2
58.0
18.0
1
32.9
27.0
2
46.4
36.0
2
59.9
54.0
2
70.8
(High Efficiency)
Standard Indoor Motor
Max Fuse Size Or
Max Circuit Breaker
2
15
20
30
15
25
30
20
25
30
40
25
35
45
60
25
35
45
60
25
35
45
60
35
50
60
80
Oversize Indoor Motor
Max Fuse Size Or
MCA
Max Circuit Breaker
2
11.9
15
20.9
25
29.9
30
13.1
15
22.1
25
30.3
35
15.0
20
22.0
25
30.1
35
38.6
40
18.1
25
31.0
35
44.5
45
58.0
60
20.9
25
32.9
35
46.4
50
59.9
60
22.9
30
32.9
35
46.4
50
59.9
60
35.4
40
48.9
50
62.4
70
73.3
80
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents