Trane Precedent RT-PRC005 User Manual page 17

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table PD-5 — Gross Cooling Capacities (MBH) 6 Ton Three Phase
Enter.
Dry
CFM
Bulb
61
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27 .3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47 .7 60.9 36.4 70.3 24.6
80
67 .6 66.2 73.7 52.2 77 .5 38.9 63.2 63.2 70.9 51.1 76.0 37 .8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9
2160
85
71.4 71.4 74.2 61.9 78.6 47 .4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67 .3 59.7 74.0 46.0 60.4 60.4 62.2 57 .3 70.8 45.0
90
74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77 .2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8
75
67 .7 58.3 74.0 43.8 77 .1 28.7 62.9 55.9 71.7 42.6 75.9 27 .7 57 .9 53.4 67 .9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0
80
69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37 .9 57 .8 57 .8 62.6 49.6 71.3 36.3
2400
85
73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77 .2 47 .9 67 .4 67 .4 69.1 63.6 74.8 47 .6 63.2 63.2 64.2 61.4 71.7 47 .0
90
76.2 76.2 76.5 74.3 79.9 57 .1 74.3 74.3 74.3 74.3 77 .9 57 .4 71.7 71.7 71.7 71.7 75.5 57 .7 68.5 68.5 68.4 68.4 72.2 57 .5
75
69.1 61.4 74.7 44.9 77 .4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4
80
71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77 .0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37 .7
2640
85
74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67 .3 77 .8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7
90
77 .4 77 .4 77 .5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8
75
70.2 64.1 75.2 45.8 77 .6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27 .3 56.2 56.2 64.7 41.9 71.7 25.8
80
72.9 72.9 75.9 57 .4 78.7 40.4 70.3 70.3 73.6 57 .8 77 .3 41.8 66.5 66.5 70.1 57 .1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5
2880
85
75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67 .8 67 .8 67 .7 67 .7 72.9 50.1
90
78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-6 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Single Compressor
Enter.
Dry
CFM
Bulb
61
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
87 .4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8
80
89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77 .6 77 .6 87 .2 65.3 97 .4 48.2 71.6 71.6 78.9 61.5 92.9 46.0
2700
85
94.2 94.2 97 .5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97 .8 61.4 78.5 78.5 80.7 76.2 93.2 59.9
90
98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5
75
89.7 78.4 96.7 57 .3 99.1 37 .2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97 .5 34.5 68.7 67 .7 80.3 50.1 93.8 32.5
80
92.2 92.2 97 .5 70.9 100.3 50.4 87 .4 87 .4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1
3000
85
96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1
90
99.5 99.5 99.9 97 .0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77 .4 90.1 90.1 90.0 90.0 95.3 77 .7
75
91.5 82.5 97 .7 59.0 99.3 37 .7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2
80
94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1
3300
85
98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97 .5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8
90
100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97 .2 97 .2 97 .2 97 .2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4
75
92.9 86.2 98.1 59.9 99.4 38.2 87 .3 84.1 96.3 60.6 99.8 37 .2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8
80
96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97 .1 77 .5 101.0 55.7 87 .6 87 .6 92.5 77 .2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6
3600
85
99.0 99.0 99.7 88.7 101.8 62.7 97 .8 97 .8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67 .3 89.1 89.1 89.1 89.1 96.3 68.3
90
101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97 .5 84.6
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT -PRC005-EN
Performance
Data
85
95
67
73
61
67
85
95
67
73
61
67
TSC072A3, A4, AW, AK
Ambient Temperature (F)
105
Entering Wet Bulb (F)
73
61
67
Ambient Temperature (F)
105
Entering Wet Bulb (F)
73
61
67
(6, 7½ Ton)
Standard Efficiency
115
73
61
67
TSC090A3, A4, AW, AK
115
73
61
67
73
73
17