Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
April 2020
S S A A F F E E T T Y Y W W A A R R N N I I N N G G
System (r-410a) mini-split, inverter system (42 pages)
Summary of Contents for Trane RAUJ-C20
Page 1
Installation, Operation, and Maintenance Split System Cooling Condensers — 20 to 120 Tons Remote Chillers — 20 to 120 Tons RAUJ-C20 RAUJ-C25 RAUJ-C30 RAUJ-C40 RAUJ-C50 RAUJ-C60 RAUJ-C80 RAUJ-D10 RAUJ-D12 S S A A F F E E T T Y Y W W A A R R N N I I N N G G Only qualified personnel should install and service the equipment.
Page 2
A A L L W W A A Y Y S S r r e e f f e e r r t t o o a a p p p p r r o o p p r r i i a a t t e e S S a a f f e e t t y y D D a a t t a a impact to the environment. Trane advocates the...
Page 3
This document and the information in it are the property of Trane, and may not be used or reproduced F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n in whole or in part without written permission.
Table of Contents Model Number Description ....7 Refrigerant Piping Components ..46 Refrigerant Piping....49 20 to 60 Ton Units .
Page 5
T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Economizer Cycle ....90 Preliminary Expansion Valve Chilled Water Temperature Adjustment .
Page 6
T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Wiring Diagrams ......128 SS-SVX11K-EN...
General Information Unit Inspection • The owner must provide reasonable evidence that the damage did not occur after delivery. To protect against loss due to damage incurred in transit, perform inspection immediately upon receipt of Repair the unit. Notify the appropriate sales representative before Exterior Inspection arranging unit installation or repair.
G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n Discharge Line Thermostat the 115V control circuit. If no faults are observed, a green LED will be energized.
Page 11
G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n Figure 2. Component layout and ‘ship-with’ locations – 20 to 60 ton units Condenser Fans Condenser...
G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n General Data Table 1. General data — RAUJ condensing units Unit Size (tons) Compressor Data Type...
Page 13
G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n Table 2. Altitude correction multiplier for capacity Altitude (ft.) Configuration 2,000...
N N o o t t e e : : EVP chiller is intended for indoor application. If a I I m m p p o o r r t t a a n n t t : : Providing less than the recommended sub-freezing location is required, contact Trane clearances could result in condenser coil...
Page 15
D D i i m m e e n n s s i i o o n n s s a a n n d d W W e e i i g g h h t t s s Table 3.
Installation Mechanical Location Requirements leveling the unit. Isolators are identified by color and/or an isolator part number. Shims under the isolators may Isolation be required if the unit cannot be leveled using the isolator leveling bolt. To minimize unit sound and vibration transmission, one of the following installation methods should be Rigging and Lifting used:...
Page 41
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Figure 28.
Page 42
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Table 6.
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Unit Isolation Neoprene Isolators (20 to 60 Ton units) Figure 31.
Check the unit for shipping damage and material shortage. If damage or shortage is found, file a For recommended components, see the latest edition freight claim and notify Trane office. of the Applications Guide SS-APG012-EN. • Verify installation location of the unit will provide the required clearance for proper operation.
Page 47
Two ball shutoff valves equal to the OD Tubing size for suction line are required. Interconnecting Liquid Line Tubing. If risers exceed 10 feet, Trane must review the Access Valves (Ports) application The access ports in the suction line allow the operating...
Page 48
Thermostatic Expansion Valve (TXV) takeoffs to the expansion valve. The sight glass should Trane recommends a balance-ported externally not be used to determine adequate refrigerant charge. equalized valve in order to maintain satisfactory...
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Table 13. Expansion valve selection, 20 to 60 ton MCHE (30% bleed) (continued) Min Tonnage Max Tonnage Selection Manufacturer Trane Part Sporlan ERZE-5-ZGA (BP/30) VAL10491 Sporlan ERZE-6-ZGA (BP/30)
Page 50
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Refrigerant piping must be properly sized and applied. N N o o t t e e : : If Suction Riser Exceeds 50 Feet, Trane Must These two factors have a very significant effect on both Review The Application.
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l Typical Field-Installed Evaporator Piping: The unit has a liquid line check valve that prevents liquid refrigerant from flowing backward through the...
The overlap distance should be equal to safety precautions. the diameter of the inner tube. Trane condensing units are shipped with a nitrogen • Wrap the body of each refrigerant line component holding charge. If there is no pressure, the unit must be with a wet cloth to keep it cool during brazing.
If a subfreezing location is required, 3. Secure the bulb to the suction line with two clamps contact Trane for installation precautions required provided by the manufacturer and insulate the bulb. to prevent damage. 4. Locate liquid line solenoid valve(s) near TXV.
D D o o n n o o t t o o p p e e r r a a t t e e w w i i t t h h w w a a t t e e r r l l o o o o p p s s w w i i t t h h l l e e s s s s t t h h a a n n f f i i v v e e a shortened heat exchanger life. Trane encourages...
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l — — E E V V P P N N o o t t e e : : Water volumes should be calculated as close as Chiller accessory kit includes strainer, water flow possible to maintain constant water flow...
Page 58
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l — — E E V V P P Braze Plate (BPHE) Chiller Strainers should be installed as close as practical to the heat exchanger water inlet (the remote chiller...
Page 59
I I n n s s t t a a l l l l a a t t i i o o n n M M e e c c h h a a n n i i c c a a l l — — E E V V P P Figure 41.
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Wiring Requirements W W A A R R N N I I N N G G P P r r o o p p e e r r F F i i e e l l d d W W i i r r i i n n g g a a n n d d G G r r o o u u n n d d i i n n g g...
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l •...
Page 65
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Disconnect Switch External Handle W W A A R R N N I I N N G G (Factory Mounted Option)
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Power Wire Sizing and Protection Devices Table 19.
Page 67
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Supply Fan Interlock W W A A R R N N I I N N G G Control Options Utilizing an Air Handler...
Page 68
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l N N O O T T I I C C E E chapter for the electrical access locations provided on the unit.
Page 69
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l panel, refer to the actual unit wiring diagram for power supply for the actuator(s) must be field terminal designation, i.e.
Page 70
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Table 25.
Page 71
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 46.
Page 72
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 47.
Page 73
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 48.
Page 74
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 49.
Page 75
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 50.
Page 76
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 51.
Page 77
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Discharge Air Sensor (Honeywell 6RT3 or economizer (if applicable) and cycling of compressors...
Page 78
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Night Setback installed across Terminals 7 &...
Page 79
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 53.
Page 80
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l •...
Page 81
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 55.
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l W W A A R R N N I I N N G G •...
Page 83
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 57. Field connection diagram - RAUJ-C20-60 - EVP chiller applications 2307-9122 N N o o t t e e : : See wiring notes on previous figure “Field...
Page 84
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l Figure 58.
Page 85
I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l W W A A R R N N I I N N G G A ground wire must be installed between the EVP remote panel and the unit control panel.
Operating Principles Component Locations Condenser Fans Figure 59. Condenser fan locations: 20 to 60 ton units 20 Ton 25 & 30 Ton Low Ambient Low Ambient Control Panel Control Panel Damper Damper 50 & 60 Ton 40 Ton Low Ambient Low Ambient Control Panel Control Panel...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s Compressors Figure 61. Compressor locations: 20 to 60 ton units 20 Ton Condensing Unit 25 &...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s Figure 64. Junction box: 80-120 Ton units Crankcase Heater HPC Wires Wires...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s Economizer Cycle When the economizer cannot handle the cooling requirement or when the outdoor ambient conditions The economizer is only allowed to function if the...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s minimum “Off” time has been satisfied (Point A). The maintain its current position, i.e., no staging of cooling minimum “fast response”...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s Table 27. RAUJ condenser fan sequencing data: 20 to 60 ton units Controlling Device Fan "ON"...
O O p p e e r r a a t t i i n n g g P P r r i i n n c c i i p p l l e e s s prevent low oil viscosity and foaming during when the ambient temperature reaches 30ºF and closes compressor starts.
Pre-Start Use the checklist provided below in conjunction with • Check the compressor oil levels. Oil levels must be the “General Unit Requirement” checklist” to ensure near or above the top of all compressor sight that the unit is properly installed and ready for glasses.
P P r r e e - - S S t t a a r r t t The oil in the vacuum pump should be changed each N N o o t t e e : : It is unlawful to release refrigerant into the time the pump is used with a high quality vacuum atmosphere.
W7100A accessory tool kit (Trane part # TOL-0101 or Honeywell part # 4074EDJ). N N o o t t e e : : It is not necessary to set the “Reset F” dial since the factory installed jumper across 1.
Page 97
P P r r e e - - S S t t a a r r t t W W A A R R N N I I N N G G switch to the “OFF” position. 21. Remove the wires from terminals R, B, W, & Y. L L i i v v e e E E l l e e c c t t r r i i c c a a l l C C o o m m p p o o n n e e n n t t s s ! ! 22.
P P r r e e - - S S t t a a r r t t Discharge Air Sensor Checkout Figure 69. W7100A discharge air controller (Honeywell Sensor) COOL W W A A R R N N I I N N G G 24 VAC H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! ! COOL...
. . checked out using a highly accurate digital voltmeter, the W7100 accessory tool kit (Trane part # TOL-0101 or 1. Turn all control switches to the “Off” position to...
P P r r e e - - S S t t a a r r t t W W A A R R N N I I N N G G Figure 71. W7100G chilled water controller L L i i v v e e E E l l e e c c t t r r i i c c a a l l C C o o m m p p o o n n e e n n t t s s ! ! COOL F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w a a l l l l e e l l e e c c t t r r i i c c a a l l s s a a f f e e t t y y p p r r e e c c a a u u t t i i o o n n s s 24 VAC...
P P r r e e - - S S t t a a r r t t N N o o t t e e : : Before condemning the sensor, verify that N N o o t t e e : : The wires that are still connected to one side the connecting cable resistance is not of the “Cool Relay”...
P P r r e e - - S S t t a a r r t t Zone Thermostat Checkout thermostat “voltage output” ramps. (Honeywell T7067) 4. To check the “Cooling” output signal, place the voltmeter leads between thermostat Terminals 1 & A A v v a a i i l l a a b b l l e e O O n n l l y y F F o o r r 2 2 0 0 - - 6 6 0 0 T T o o n n U U n n i i t t s s 4.
Page 103
P P r r e e - - S S t t a a r r t t 1. Turn the control circuit switch 1S2, in the unit 6RT1 is out of range; replace it. control panel, to the “OFF” position. N N o o t t e e : : Before condemning the sensor, verify that 2.
P P r r e e - - S S t t a a r r t t Electrical Phasing Figure 73. W973 master energy controller (MEC) W W A A R R N N I I N N G G HEAT H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! ! F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d...
Start-Up Low Ambient Damper To check damper operation, jumper between the sensor input terminals 6 and 7 and/or 11 and 12 (if Adjustment applicable). Controller output signal will go to 10 VDC (Factory or Field Installed) and damper will drive to full open position. When a unit is ordered with the low ambient option EVP Chiller Applications (model number digit 11 =1), a damper is factory...
S S t t a a r r t t - - U U p p Measuring Airflow W W A A R R N N I I N N G G L L i i v v e e E E l l e e c c t t r r i i c c a a l l C C o o m m p p o o n n e e n n t t s s ! ! With the supply fan rotating in the proper direction, measure the amperage at the supply fan contactor.
S S t t a a r r t t - - U U p p Preliminary Expansion Valve leaving the evaporator at nominal design conditions. Thermal expansion valves with bleeds are set to their Adjustment highest superheat setting. Actual superheat depends on many factors (valve vs.
S S t t a a r r t t - - U U p p Table 32. Thermal expansion valve manufacturer settings - no bleed — Danfoss Standard off the shelf nominal valve settings Field adjust Field adjust Superheat for 18°F (DX for 15°F CW turns...
S S t t a a r r t t - - U U p p N N O O T T I I C C E E I I m m p p o o r r t t a a n n t t : : Do not attempt to charge the system with the low ambient dampers and/or hot gas C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! ! bypass operating (if applicable).
Page 110
S S t t a a r r t t - - U U p p outdoor temperatures. If the outdoor temperature is could be improperly phased. A main unit power less than 80°F, temporarily disable the fan pressure phase protection module (1U3) is located in the control switches (4S11, 4S12) or (4S7, 4S8) on 80 - RAUJ control box and interrupts control circuit 120 Ton units.
Page 111
S S t t a a r r t t - - U U p p g. Subtract the total charge already added from at this time. Follow the procedures discussed the table in Preliminary Charging section charge earlier to confirm proper rotation of these estimate for condensing unit at the appropriate condenser fans.
S S t t a a r r t t - - U U p p Figure 74. System charging chart (all units) 150" lines 50’ lines 150’ lines Remove Charge Add Charge Add Charge Add Charge Add Charge Liquid Line Temp at Outdoor Unit, °F Motors Rotating Backward W W A A R R N N I I N N G G H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
"Off" position. Lock the N N o o t t e e : : On many Trane fan/coil units, an access valve disconnect switch in the open position while is provided close to the expansion valve bulb working at the unit.
S S t t a a r r t t - - U U p p Table 36. Pressure control switch settings (psi) Table 37. Compressor sequence: 20-120 Ton units (continued) Pressure Switch Make Break Control Unit % Loaded Hi Pressure Step Size Circuit 1...
Page 115
S S t t a a r r t t - - U U p p Figure 76. 25 Ton cooling cycle pressure curve Figure 79. 50 Ton cooling cycle pressure curve 25T Cooling Cycle Pressure Curve 50T Cooling Cycle Pressure Curve All compressors and condenser fans running All compressors and condenser fans running 105°F OD...
S S t t a a r r t t - - U U p p Final System Setup Figure 82. 100 Ton cooling cycle pressure curve W W A A R R N N I I N N G G 100T Cooling Cycle Pressure Curve All compressors and condenser fans running H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
Page 117
S S t t a a r r t t - - U U p p SS-SVX11K-EN...
Page 118
S S t t a a r r t t - - U U p p SS-SVX11K-EN...
Maintenance Monthly Maintenance I I m m p p o o r r t t a a n n t t : : Use a hand grease gun to lubricate bearings. Add grease until a light bead Air Handling Equipment appears all around the seal.
Water Strainer Maintenance Trane Parts Center. N N o o t t e e : : DO NOT use any detergents with To protect the evaporator and for maximum efficiency, microchannel coils.
The following discussion describes some of the operational sounds of Trane R-410A scroll F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n compressors.
M M a a i i n n t t e e n n a a n n c c e e N N O O T T I I C C E E a dedicated device for removing oil. It is good practice to flush the suction device with clean oil prior to use.
M M a a i i n n t t e e n n a a n n c c e e Precision Suction Restrictor Charge the new oil into the Schrader valve or oil drain valve on the shell of the compressor. Due to the RAUJ tandems with unequal compressors and all moisture absorption properties of POE oil, do not use RAUJ trios use precision suction restrictors to balance...
Page 124
M M a a i i n n t t e e n n a a n n c c e e Table 43. Compressor circuit breakers (200-230 volts) (continued) Must Trip Must Hold Voltage 1A / 2A 1B / 2B 1C / 2C 1A / 2A 1B / 2B...
M M a a i i n n t t e e n n a a n n c c e e Suction Line Filter Figure 88. Suction line filter installation: 80 to120 Ton units Figure 87. Suction line filter installation: 20 to 60 Ton units 25”...
M M a a i i n n t t e e n n a a n n c c e e Fall Restraint — Condenser Roof Figure 89. Fall restraint slot W W A A R R N N I I N N G G F F a a l l l l i i n n g g O O f f f f E E q q u u i i p p m m e e n n t t ! ! F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y .
This warranty* is extended by Trane Inc. and applies including implied warranties of merchantability and only to commercial equipment rated 20 Tons and fitness for particular use.
Page 128
Wiring Diagrams N N o o t t e e : : Published unit wiring diagrams (individual, separate diagrams for unitary product lines) are available via e-Library. Drawing Description Number Unit Connection Wiring Split - System Condensing Unit Air Cooled RAUJ 20-60 Ton units 2307-4483 Connection-Adder Plates Split System Condensing Unit RAUJ 80-120 Ton units 2307-4495...
Page 132
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.