Trane Precedent RT-PRC005 User Manual page 33

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table PD-33— Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —DownflowAirflow
.10
.20
CFM
RPM
BHP
RPM
BHP
2720
3060
3400
612
0.68
3740
622
0.76
659
0.86
4080
671
0.96
706
1.08
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-33 — Continued
1.10
1.20
CFM
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
2720
863
1.48
892
1.63
3060
891
1.66
919
1.81
3400
917
1.87
946
2.03
3740
945
2.11
974
2.28
4080
976
2.38
1002
2.56
Table PD-34 — Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —Horizontal Airflow
.10
.20
CFM
RPM
BHP
RPM
BHP
2720
598
0.57
3060
616
0.69
654
0.77
3400
675
0.92
711
1.01
3740
735
1.20
770
1.30
4080
796
1.53
828
1.65
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-34 — Continued
1.10
1.20
CFM
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
2720
956
1.67
982
1.79
3060
999
1.99
1026
2.12
3400
1034
2.32
1067
2.49
3740
1063
2.63
1098
2.84
4080
1093
2.99
1125
3.19
RT -PRC005-EN
Performance
Data
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
RPM
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
613
0.60
655
611
0.64
650
0.74
688
651
0.79
689
0.91
724
693
0.97
729
1.10
764
738
1.19
770
1.32
804
External Static Pressure (Inches of Water)
1.30
1.40
RPM
BHP
RPM
BHP
RPM
920
1.78
946
1.93
973
946
1.96
973
2.12
999
974
2.18
1001
2.34
1026
1001
2.44
1028
2.61
1054
1029
2.73
1055
2.91
1081
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
RPM
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
646
0.67
689
0.78
734
693
0.86
735
0.98
773
743
1.10
781
1.22
819
799
1.40
830
1.51
865
857
1.76
883
1.86
913
External Static Pressure (Inches of Water)
1.30
1.40
RPM
BHP
RPM
BHP
RPM
1008
1.91
1033
2.03
1056
1052
2.26
1078
2.39
1101
1094
2.64
1120
2.79
1145
1129
3.03
1158
3.21
1185
1157
3.40
(8½ Ton)
Standard Efficiency
.50
.60
.70
BHP
RPM
BHP
RPM
0.72
695
0.84
733
0.85
725
0.98
761
1.02
759
1.15
792
1.23
795
1.35
826
1.46
834
1.60
864
Trane's factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
1.50
1.60
1.70
BHP
RPM
BHP
RPM
3-HP Oversized Motor & Drive
2.08
999
2.24
1025
2.29
1024
2.46
1048
2.52
1051
2.69
1074
2.78
1079
2.96
1103
3.09
1105
3.26
1130
.50
.60
.70
BHP
RPM
BHP
RPM
0.90
781
1.04
826
1.10
812
1.23
855
1.36
853
1.49
886
1.65
899
1.79
930
1.99
945
2.15
977
Trane's factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
1.50
1.60
1.70
BHP
RPM
BHP
RPM
3-HP Oversized Motor & Drive
2.14
1079
2.26
1102
2.52
1124
2.66
1146
2.94
1168
3.09
1191
3.39
.80
.90
BHP
RPM
BHP
RPM BHP
2-HP Standard Motor
& Drive
0.95
769
1.08
802
1.21
1.11
796
1.25
828
1.38
1.29
825
1.43
856
1.58
1.49
857
1.64
887
1.79
1.74
892
1.88
920
2.04
1.80
1.90
BHP
RPM
BHP
RPM
BHP
2.39
1050
2.55
1073
2.71
2.63
1072
2.80
1096
2.98
2.86
1099
3.05
1121
3.23
3.14
1126
3.32
3.45
.80
.90
BHP
RPM
BHP
RPM BHP
2-HP Standard Motor & Drive
1.18
865
1.31
898
1.44
1.39
897
1.55
934
1.70
1.62
925
1.79
964
1.97
1.94
960
2.09
994
2.26
2.30
1006
2.47
1034 2.63
3-HP Oversized Motor & Drive
1.80
1.90
BHP
RPM
BHP
RPM
BHP
2.38
1125
2.50
1146
2.62
2.79
1168
2.92
1188
3.05
3.24
1213
3.39
1.00
RPM BHP
833
1.34
861
1.52
887
1.72
916
1.96
948
2.20
2.00
RPM
BHP
1098
2.88
1119
3.14
1143
3.41
1.00
RPM BHP
928
1.56
969
1.85
1000 2.14
1028 2.44
1061 2.79
2.00
RPM
BHP
1168
2.74
1209
3.18
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents