Trane Precedent RT-PRC005 User Manual page 56

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table ED-7 — Unit Wiring With Electric Heat (Single Point Connection) — 208/230 Volts — High Efficiency
To Use
Heater
Tons
With
Model No.
BAYHTRR105A
3
THC036A1
BAYHTRR110A
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
4
THC048A1
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
5
THC060A1
BAYHTRR114A
BAYHTRR118A
BAYHTRR306A
3
THC036A3
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
4
THC048A3
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
5
THC060A3
BAYHTRR318A
BAYHTRR323A
BAYHTRS309A
6
THC072A3
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
BAYHTRT309A
THC092A3
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT309A
THC102A3
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT318A
10
THC120A3
BAYHTRT327A
BAYHTRT336A
BAYHTRT354A
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
56
Electrical
Data
Standard Indoor Motor
Heater
Control
kW Rating
1
Stages
MCA
208/230 Volts Single Phase
3.8/5.0
1
25.5/28.9
7.5/10.0
2
48.0/55.0
10.4/13.8
2
65.1/74.8
3.8/5.0
1
29.4/30.5
7.5/10.0
2
49.6/56.6
10.4/13.8
2
66.8/76.4
13.2/17.6
2
84.0/96.1
3.8/5.0
1
39.5/39.5
7.5/10.0
2
52.9/59.9
10.4/13.8
2
70.0/79.6
13.2/17.6
2
87.3/99.4
208/230 Volts Three Phase
4.5/6.0
1
18.5/20.9
9.0/12.0
2
34.1/39.0
13.1/17.4
2
48.3/55.3
4.5/6.0
1
21.2/22.5
9.0/12.0
2
35.8/40.6
13.1/17.4
2
49.9/56.9
4.5/6.0
1
30.0/30.0
9.0/12.0
2
39.0/43.9
13.1/17.4
2
53.1/60.1
17.3/23.0
2
67.8/76.9
6.8/9.0
1
34.8/34.8
13.5/18.0
1
53.1/60.4
20.3/27.0
2
76.6/87.5
27.0/36.0
2
100.1/114.5
6.8/9.0
1
38.1/38.1
13.5/18.0
1
54.8/62.0
20.3/27.0
2
78.3/89.1
27.0/36.0
2
101.8/116.1
6.8/9.0
1
42.3/42.3
13.5/18.0
1
54.8/62.0
20.3/27.0
2
78.3/89.1
27.0/36.0
2
101.8/116.1
13.5/18.0
1
58.6/65.9
20.3/27.0
2
82.1/93.0
27.0/36.0
2
105.6/120.0
40.6/54.0
2
152.5/141.7
(High Efficiency)
Oversize Indoor Motor
Max Fuse Size Or
Max Circuit Breaker
2
MCA
40/40
28.5/31.9
50/60
51.0/58.0
70/80
68.1/77.8
45/45
31.5/33.1
50/60
52.3/59.3
70/80
69.4/79.0
90/100
86.6/98.8
60/60
41.2/41.2
60/60
55.0/62.0
80/80
72.1/81.8
90/100
89.4/101.5
25/25
21.5/23.9
35/40
37.1/42.0
50/60
51.3/58.3
30/30
23.3/25.1
40/45
38.4/43.3
50/60
52.5/59.5
45/45
31.7/31.7
45/45
41.1/46.0
60/70
55.3/62.3
70/80
69.9/79.0
50/50
35.7/35.7
60/70
54.8/62.0
80/90
78.3/89.1
110/125
101.8/116.1
50/50
44.2/44.2
60/70
58.6/65.9
80/90
82.1/93.0
110/125
105.6/120.0
50/50
44.2/44.2
60/70
58.6/65.9
80/90
82.1/93.0
110/125
105.6/120.0
60/70
63.6/70.9
90/100
87.1/98.0
110/125
110.6/125.0
175/150
157.5/146.7
Max Fuse Size Or
Max Circuit Breaker
2
40/40
60/60
70/80
50/50
60/60
70/80
90/100
60/60
60/70
80/90
90/100
25/25
40/45
60/60
35/35
40/45
60/60
45/45
45/50
60/70
70/80
50/50
60/70
80/90
110/125
50/50
60/70
90/100
110/125
50/50
60/70
90/100
110/125
70/80
90/100
125/125
175/150
RT -PRC005-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents