(2) Layout of main circuit terminals
The figures below show the terminal layout on the main circuit terminal block of the inverter.
Ground terminal with jumper (shaded in the
フィルタ機能
figure) to enable/disable the EMC filter function
切り替え用短絡片
[Method of enabling/disabling the EMC filter function]
斜線部 付き接地端子
Enabling the EMC filter
Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function
[Method of enabling/disabling the EMC filter function]
Enabling the EMC filter
Terminal layout
チャージランプ
Charge lamp
Jumper
短絡片
connecting
terminals PD
When not using the DCL,
を使用 しない場合、
do not remove the jumper
短絡 片を取り外さ
from terminals PD and P.
ないでくださ い。
Disabling the EMC filter
(factory setting)
Charge lamp
Jumper connecting
terminals PD and P
When not using the DCL,
do not remove the jumper
from terminals PD and P.
Disabling the EMC filter
(factory setting)
2 - 13
Chapter 2 Installation and Wiring
Inverter model
L700-110LFF
L700-110HFF
R0 and T0: M4
Ground terminal: M5
Other terminals: M5
L700-150LFF
L700-150HFF
R0 and T0: M4
Ground terminal: M5
Other terminals: M6
L700-185 to
L700-220LFF
L700-185 to
L700-300HFF
R0 and T0: M4
Ground terminal: M6
Other terminals: M6
L700-300LFF
R0 and T0: M4
Ground terminal: M6
Other terminals: M8