Chapter 2 Installation and Wiring
(9) Reduction of enclosure size
If you mount the inverter inside an enclosure such that the heat sink of the inverter is positioned
outside the enclosure, the amount of heat produced inside the enclosure can be reduced and likewise
the size of the enclosure.
Mounting the inverter in an enclosure with the heat sink positioned outside requires an optional
dedicated special metal fitting.
To mount the inverter in an enclosure with the heat sink positioned outside, cut out the enclosure panel
according to the specified cutting dimensions.
The cooling section (including the heat sink) positioned outside the enclosure has a cooling fan.
Therefore, do not place the enclosure in any environment where it is exposed to waterdrops, oil mist,
or dust.
(10) Approximate loss by inverter capacity
Inverter capacity (kW)
Loss with 70% load (W)
Loss with 100% load (W)
Efficiency at rated output (%)
11
15
18.5
22
435
575
698
820
600
800
975
1150
94.8
94.9
95.0
95.0
30
37
45
55
1100
1345
1625
1975
1550
1900
2300
2800
95.0
95.1
95.1
95.1
2 - 4
75
90
110
132
2675
3375
3900
4670
3800
4800
5550
6650
95.2
95.2
95.2
95.2
160
5660
8060
95.2