Hitachi L700 SERIES Instruction Manual page 252

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Chapter 8 List of Data Settings
Code
Function name
C021
Terminal [11] function
C022
Terminal [12] function
C023
Terminal [13] function
C024
Terminal [14] function
C025
Terminal [15] function
C026
Alarm relay terminal function
C027
[FM] siginal selection
C028
[AM] siginal selection
C029
[AMI] siginal selection
Digital current monitor reference
C030
value
C031
Terminal [11] active state
C032
Terminal [12] active state
C033
Terminal [13] active state
C034
Terminal [14] active state
C035
Terminal [15] active state
C036
Alarm relay active state
Monitored data or setting
00 (RUN: running), 01 (FA1: constant-speed reached),
02 (FA2: set frequency overreached),
03 (OL: overload notice advance signal (1)),
04 (OD: output deviation for PID control), 05 (AL: alarm signal),
06 (FA3: set frequency reached), 07 (OTQ: over-torque),
08 (IP: instantaneous power failure), 09 (UV: undervoltage),
10 (TRQ: torque limited), 11 (RNT: operation time over),
12 (ONT: plug-in time over), 13 (THM: thermal alarm signal),
21 (ZS: 0 Hz detection signal), 24 (FA4: set frequency overreached 2),
25 (FA5: set frequency reached 2),
26 (OL2: overload notice advance signal (2)),
27 (Odc: Analog O disconnection detection),
28 (OIDc: Analog OI disconnection detection),
29 (O2Dc: Analog O2 disconnection detection),
31 (FBV: PID feedback comparison),
32 (NDc: communication line disconnection),
33 (LOG1: logical operation result 1),
34 (LOG2: logical operation result 2),
35 (LOG3: logical operation result 3),
36 (LOG4: logical operation result 4),
37 (LOG5: logical operation result 5),
38 (LOG6: logical operation result 6),
39 (WAC: capacitor life warning), 40 (WAF: cooling-fan speed drop),
41 (FR: starting contact signal), 42 (OHF: heat sink overheat warning),
43 (LOC: low-current indication signal),
44 (M01: general-purpose output 1), 45 (M02: general-purpose output
2), 46 (M03: general-purpose output 3),
47 (M04: general-purpose output 4),
48 (M05: general-purpose output 5),
49 (M06: general-purpose output 6), 50 (IRDY: inverter ready),
51 (FWR: forward rotation), 52 (RVR: reverse rotation),
53 (MJA: major failure), 54(WCO: window comparator O),
55(WCOI: window comparator OI),
56 (WCO2: window comparator O2)
(When alarm code output is selected for "C062", functions "AC0" to
"AC2" or "AC0" to "AC3" [ACn: alarm code output] are forcibly assigned
to intelligent output terminals 11 to 13 or 11 to 14, respectively.)
00 (output frequency), 01 (output current), 02 (output torque),
03 (digital output frequency), 04 (output voltage), 05 (input power),
06 (electronic thermal overload), 07 (LAD frequency),
08 (digital current monitoring), 09 (motor temperature),
10 (heat sink temperature), 12 (general-purpose output YA0)
00 (output frequency), 01 (output current), 02 (output torque),
04 (output voltage), 05 (input power), 06 (electronic thermal overload),
07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature),
11 (output torque [signed value]), 13 (general-purpose output YA1)
00 (output frequency), 01 (output current), 02 (output torque),
04 (output voltage), 05 (input power), 06 (electronic thermal overload),
07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature),
14 (general-purpose output YA2)
0.20 x "rated current" to 1.50 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
8 - 10
Setting
Change
Default
during
during
operation
operation
Page
(allowed
(allowed
_FF
or not)
or not)
01
00
03
4-62
07
40
05
00
4-76
00
4-77
00
Rated
current
4-75
of
inverter
00
00
00
4-63
00
00
01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents