Hitachi L700 SERIES Instruction Manual page 191

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

(iii) List of registers (monitoring)
Register
Function name
No.
1001h
Output frequency monitoring
1002h
1003h
Output current monitoring
1004h
Rotation direction minitoring
1005h
Process variable (PV), PID
1006h
feedback monitoring
1007h
Intelligent input terminal status
Intelligent output terminal
1008h
status
1009h
Scaled output frequency
100Ah
monitoring
100Bh
Actual-frequency monitoring
100Ch
100Dh
Torque command monitoring
100Eh
Torque bias monitoring
100Fh
(Reserved)
1010h
Torque monitoring
1011h
Output voltage monitoring
1012h
Power monitoring
1013h
Cumulative power monitoring
1014h
1015h
Cumulative operation RUN
time monitoring
1016h
1017h
Cumulative power-on time
monitoring
1018h
Heat sink temperature
1019h
monitoring
101Ah
Motor temperature monitoring
101Bh
(Reserved)
101Ch
101Dh
Life-check monitoring
101Eh to
(Reserved)
1025h
DC voltage monitoring (across
1026h
P and N)
1027h
BRD load factor monitoring
Electronic thermal overload
1028h
monitoring
1029h to
(reserved)
102Dh
102Eh
User monitor 1
102Fh
1030h
User monitor 1
1031h
1032h
User monitor 1
1033h
1034h
Pulse counter
1035h
1036h
Position setting monitor
1037h
1038h
Position feedback monitor
1039h
103Ah to
Unused
1102h
(iv) List of registers
Register
Function name
No.
1103h
Acceleration (1) time setting
1104h
1105h
Deceleration (1) time setting
1106h
1107h
Keypad Run key routing
1108h to
Unused
1200h
Function code
R/W
d001 (high)
R
0 to 40000
d001 (low)
d002
R
0 to 9999
0: Stopping, 1: Forward rotation, 2: Reverse
d003
R
rotation
d004 (high)
R
0 to 9990
d004 (low)
d005
R
2^0: Terminal 1 to 2^7: Terminal 8
d006
R
2^0: Terminal 11 to 2^4: Terminal 15
d007 (high)
R
0 to 39960
d007 (low)
d008 (high)
R
-40000 to +40000
d008 (low)
R
d009
R
-200 to +200
d010
R
-200 to +200
-
-
Inaccessible
d012
R
-200 to +200
d013
R
0 to 6000
d014
R
0 to 9999
d015 (high)
R
0 to 9999999
d015 (low)
d016 (high)
R
0 to 999900
d016 (low)
d017 (high)
R
0 to 999900
d017 (low)
d018
R
-200 to 2000
d019
R
-200 to 2000
-
-
Inaccessible
2^0: Capacitor on main circuit board
d022
R
2^1: Low cooling-fan speed
-
-
Inaccessible
d102
R
0 to 9999
d103
R
0 to 1000
d104
R
0 to 1000
-
-
Inaccessible
d025(HIGH)
R
-2147483647 to 2147483647
d025(LOW)
R
d026(HIGH)
R
-2147483647 to 2147483647
d026(LOW)
R
d027(HIGH)
R
-2147483647 to 2147483647
d027(LOW)
R
d028(HIGH)
R/W
0 to 2147483647
d028(LOW)
R/W
d029(HIGH)
R
-2147483647 to 2147483647
d029(LOW)
R
d030(HIGH)
R
-2147483647 to 2147483647
d030(LOW)
R
-
Inaccessible
Function code
R/W
F002 (high)
R/W 1 to 360000
F002 (low)
F003 (high)
R/W 1 to 360000
F003 (low)
F004
R/W 0 (forward rotation), 1 (reverse rotation)
-
-
Inaccessible
4 - 129
Chapter 4 Explanation of Functions
Monitoring and setting items
Monitoring and setting items
Data
resolution
0.01 [Hz]
0.1 [A]
0.1 [Hz]
0.1
1 bit
1 bit
0.01
0.01 [Hz]
1 [%]
1 [%]
-
1 [%]
0.1 [V]
0.1 [kW]
0.1
0.1
1 [h]
0.1 [ ]
0.1 [ ]
-
1 bit
-
0.1 [V]
0.1 [%]
0.1 [%]
-
1
1
1
1
1
1
-
Data
resolution
0.01 [sec.]
0.01 [sec.]
-
-