Hitachi L700 SERIES Instruction Manual page 253

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Code
Function name
Low-current indication signal output
C038
mode selection
Low-current indication signal
C039
detection level
C040
Overload signal output mode
C041
Overload level setting
C042
Frequency arrival setting for accel.
C043
Frequency arrival setting for decel.
C044
PID deviation level setting
Frequency arrival setting for
C045
acceleration (2)
Frequency arrival setting for
C046
deceleration (2)
C052
Maximum PID feedback data
C053
Minimum PID feedback data
Over-torque (forward-driving)
C055
level setting
Over-torque (reverse regenerating)
C056
level setting
Over-torque (reverse driving)
C057
level setting
Over-torque (forward regenerating)
C058
level setting
Electronic thermal warning
C061
level setting
C062
Alarm code output
C063
Zero speed detection level
C064
Heat sink overheat warning level
C071
Communication speed selection
C072
Node allocation
C073
Communication data length selection
C074
Communication parity selection
C075
Communication stop bit selection
Selection of the operation after
C076
communication error
Communication timeout limit before
C077
tripping
C078
Communication wait time
C079
Communication mode selection
C081
[O] input span calibration
C082
[OI] input span calibration
C083
[O2] input span calibration
C085
Thermistor input tuning
C091
Debug mode enable
C101
Up/Down memory mode selection
C102
Reset mode selection
C103
Restart mode after reset
C105
FM gain adjustment
C106
AM gain adjustment
C107
AMI gain adjustment
C109
AM bias adjustment
C110
AMI bias adjustment
(Note)<>indicate the setting range of 90 to 160kW
Monitored data or setting
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
0.0 to 1.50 x "rated current" (A)
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
0.0 to 1.50 x "rated current" (A) <0.0 to 1.50 x "rated current">
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.0 to 100.0 (%)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
0. to 150. (%)
0. to 150. (%)
0. to 150. (%)
0. to 150. (%)
0. to 100. (%)
00 (disabling), 01 (3 bits), 02 (4 bits)
0.00 to 99.99, 100.0 (Hz)
0. to 200.0 ( C)
02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps),
06 (19,200 bps)
1. to 32.
7 (7 bits), 8 (8 bits)
00 (no parity), 01 (even parity), 02 (odd parity)
1 (1 bit), 2 (2 bits)
00 (tripping), 01 (tripping after decelerating and stopping the motor),
02 (ignoring errors), 03 (stopping the motor after free-running),
04 (decelerating and stopping the motor)
0.00 to 99.99 (s)
0. to 1000. (ms)
00(ASCII), 01(Modbus-RTU)
0. to 9999., 1000 to 6553(10000 to 65530)
0. to 9999., 1000 to 6553(10000 to 65530)
0. to 9999., 1000 to 6553(10000 to 65530)
0.0 to 999.9, 1000.
(Do not change this parameter, which is intended for factory adjustment.)
00 (not storing the frequency data), 01 (storing the frequency data)
00 (resetting the trip when RS is on),
01 (resetting the trip when RS is off),
02 (enabling resetting only upon tripping [resetting when RS is on]),
03(resetting only trip)
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
50. to 200. (%)
50. to 200. (%)
50. to 200. (%)
0. to 100. (%)
0. to 100. (%)
8 - 11
Chapter 8 List of Data Settings
Setting
Default
during
operation
(allowed
_FF
or not)
01
Rated
current
of
inverter
01
Rated
current
of
inverter
0.00
0.00
3.0
0.00
0.00
100.0
0.0
100.
100.
100.
100.
80.
00
0.00
120.
04
1.
7
00
1
02
0.00
0.
00
Factory
setting
Factory
setting
Factory
setting
Factory
setting
00
00
00
00
100.
100.
100.
0.
20.
Change
during
operation
Page
(allowed
or not)
4-72
4-40
4-64
4-26
4-64
4-26
4-67
4-37
4-68
4-66
4-71
4-97
4-75
4-57
4-55
4-76
4-77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents