The commons associated with each form C Relay (R0COM and R1COM) have the option of
being tied to the ControlWave EFM Power Ground or to a floating Ground. Jumper W1 is
associated with Outputs R0A and R0B and W2 is associated with outputs R1A and R1B.
When Jumper W1 is installed the common (C) associated with Outputs R0A and R0B is tied
to ControlWave EFM Power ground; when Jumper W1 is not installed, the common will
be floating. When Jumper W2 is installed the common (C) associated with Outputs R1A and
R1B is tied ControlWave EFM Power ground; when Jumper W2 is not installed, the
common will be floating.
Table 2-14 - Jumper Settings versus Form C Relay Output States
JUMPERS
R0A
W3/W5
STATE
IN/OUT
NO
OUT/IN
NC
Table 2-13 provides the relationship between Jumper settings and Form C Relay Outputs.
Table 2-15 - Digital To Relay I/O Board Connections to J1/P1
J1 Pin
Signal
1
R1B
2
R1A
3
R1COM
4
CHASSIS GND
5
R0COM
6
ROB
7
ROA
8
-
9
POWER GND
10
POWER - DC
11
DOUT0
12
DOUT1
The DI/DO Module and the Mixed I/O Module provide independently firmware controlled
open drain outputs, which can be used for control or signaling functions (DI/DO Modules
provide up to four DO while the Mixed I/O Module provides up to 6 DO). Each output is
wired to the source terminal of an N Channel MOSFET capable of switching up to 16 Volts
at up to 100mA. When closed, the FET shorts the output to ground with resistance of .5
Ohms or less. These outputs are protected by 16V Transorbs. Since these outputs are not
isolated, caution must be exercised to ensure that the load current does not affect operation
of the ControlWave EFM or related devices.
Two of these outputs may be wired to field circuitry via the Digital to Relay I/O Board
option (see Figure 2-28). Table 2-15 provides the wiring connections for the DI/O Module or
the Mixed I/O Module and the Digital to Relay I/O Board.
CI-ControlWave EFM
JUMPERS
R0B
W4/46
STATE
IN/OUT
NO
OUT/IN
NC
Function
Relay 1 Output B
Relay 1 Output A
Relay 1 Common
Chassis Ground
Relay 0 Common
Relay 0 Output B
Relay 0 Output A
-
Power Ground
Power - 6/12 Vdc
Discrete Output 0
Discrete Output 1
JUMPERS
R1A
W7/W9
STATE
IN/OUT
NO
OUT/IN
NC
Wiring Connections
To Field
To Field
To Field (See W2)
CWMICRO Chassis Gnd. Lug
To Field (See W1 - Section 1.1.1)
To Field
To Field
Pwr. Dist. Bd.
TB4 Pin 2 (Black Wire)
Pwr. Dist. Bd.
TB4 Pin 1 (Red Wire)
DI/O Module TB2-5 - TB2-8 or
Mixed I/O Module TB1-1 - TB1-6 (Yellow Wire)
DI/O Module TB2-6 - TB2-8 or
Mixed I/O Module TB1-2 - TB1-6 (Orange
Wire)
Installation & Operation / 2-41