Download Print this page

Cpu Module Leds; System Controller Module (Scm) - Emerson ControlWave EFM 4710A Instruction Manual

Emerson electronic flow meter instruction manual

Advertisement

Table 1-3 - Assignment of CPU Bd. Switch SW1
Switch
SW1-3
Force Recovery Mode
Table 1-4 - Assignment of CPU Module Switch SW3
Switch
SW3-1
SW3-2
SW3-3
SW3-4
SW3-7
SW3-8

1.3.2.5 CPU Module LEDs

ControlWave EFM CPU Modules have six (6) LEDs on the CPU Board. Units equipped
with an optional Ethernet Port have two (2) additional LEDs (situated on the Ethernet RJ-
45 connector). Table 1-5 provides CPU Module LED assignments. An ON LED indicates an
associated transmit (TX) or receive (RX) activity.

1.3.3 System Controller Module (SCM)

The System Controller Module (SCM) plugs into the system's Backplane Board slot #1
(Connector P1 - a 44-pin female non-keyed header). The front of the SCM contains two
pluggable terminal blocks for external, input power (TB1) and RTD (TB2 - future) connec-
tions. An RJ-45 connector provides the interface to a remote Display/Keypad Assembly. Two
red LEDs, visible through the front panel, provide for the following status conditions when
lit: WD (Indicates a Watchdog condition has been detected) & IDLE (Indicates that the
CPU has free time at the end of its execution cycle. Normally, it should be ON most of the
time. When the Idle LED is OFF, it indicates that the CPU has no free time, and may be
overloaded). Six status LEDs provide run time status codes.
SCMs contain a DC to DC power supply that generates a +3.3Vdc supply for the entire unit,
i.e., the CPU and various I/O Modules that plug into the Backplane Board. Also contained
on the SCM is the sequencer circuit that monitors the external power supply as well as the
logic supplies (3.3Vdc and 1.8Vdc on the CPU Board). The sequencer circuit has a
reset/early power fail warning controller that is utilized by the CPU Board to generate a
master reset (MRESET) to the rest of the system and to generate a power fail interrupt to
the CPU.
1-12 / Introduction
Force Recovery Mode
Function
Loopback & Termination Control
COM3 -
RS-485 Function
TX+ to RX+ Loopback
TX- to RX- Loopback
100 Ohm RX+ Termination
100 Ohm RX- Termination
RX+ Bias (End Node)
RX- Bias (End Node)
Table 1-5 - Assignment of CPU Module LEDs
LED Ref.
C1
C1
C2
C2
C3
C3
Setting
ON = Force recovery mode (via CW Console)
OFF = Recovery mode disabled
Setting
ON - Only for Diagnostics
ON - Only for Diagnostics
ON - End Nodes Only
ON - End Nodes Only
ON - End Nodes Only
ON - End Nodes Only
LED Function
TX COM1
RX COM1
TX COM2
RX COM2
TX COM3
RX COM3
CI-ControlWave EFM