Electrical isolation:
Surge Suppression:
Status Indication:
Power Consumption:
4.5 DIGITAL TO RELAY I/O BOARD SPECIFICATIONS
Digital to Relay I/O Board General Specs.
Terminations:
Digital to Relay I/O Board Input Requirements
Power Source Range:
SSR Input Impedance:
MOSFET Sink Current:
Digital to Relay I/O Board Output Requirements
Contact Ratings:
Maximum Current:
Maximum ON State:
Minimum Current Load:
4.6 21V POWER SUPPLY BOARD SPECIFICATIONS
21V Power Supply Board General Specs.
Terminations:
ESD Susceptibility:
EMI Compatibility:
Transient Susceptibility:
CI-ControlWave EFM
None
31V Transorb between signal and ground
Meets ANSI/IEEE C37.90-1978
None
200uA or 2mA per HSCSET or HSCRST Input (ON State)
(Jumper Selectable per Point)
(Clock Power Disabled - Subtract 1.1mA @ 3.3V)
Pluggable - Max. wire size is 14 gauge
3 to 15 Vdc
400 Ohms
Max. = 20mA (both SSRs in Normally Closed mode)
3 to 60 Vdc
3 Amps at 25°C (77°F) or 1.5 Amps at 70°C (158°F)
1.2Vdc
100mA
Pluggable - Max. wire size is 14 gauge
Field connected circuits meet the requirements of IEC 801-
2 for withstand capability up to 10KV.
Designed to coexist within a shielded enclosure with the
ControlWave EFM electronics. EMI radiation is in-
significant and susceptibility is comparable or superior to
associated electronics.
Field
connected
circuits
ANSI/IEEEC37.90-1998 (Formerly IEEE 472) for surge
withstand capability.
meet
the
requirements
Specifications / 4-9