Download Print this page

Diagnostics Using Windiag; Communications Diagnostic Port Loop-Back Test - Emerson ControlWave EFM 4710A Instruction Manual

Emerson electronic flow meter instruction manual

Advertisement

4. Select the module to be tested. Enter any prompted parameters (slot #, etc.). WINDIAG
will perform the diagnostics and display pass/fail results.
5. After all diagnostic testing has been performed, exit the WINDIAG program and then
exit the Netview Program if there aren't any other ControlWave EFM units to be
tested.
When you close the Netview program you will be prompted as to whether or not you
want to close the OpenBSI program; select Yes.
6. Set the ControlWave EFM CPU Switch SW2-8 to the ON (Open) position. The
ControlWave EFM should resume normal operation.

3.5.1 Diagnostics Using WINDIAG

All ControlWave EFM Modules except the System Controller Module can be tested using
the WINDIAG program. From WINDIAG's Main Diagnostics Menu (see Figure 3-8) the
following diagnostic tests can be performed:
CPU & Peripherals Diagnostic:
PROM/RAM Diagnostic:
Communications Diagnostic:
Analog Output Diagnostic:
Analog Input Diagnostic:
Discrete I/O Diagnostic:
High Speed Counter Diagnostic:

3.5.1.1 Communications Diagnostic Port Loop-back Test

WINDIAG's Communications Diagnostic Menu (see Figure 3-11) provides for selection of
the communication port to be tested. Depending on the type of network (RS-232 or RS-485)
and the port in question, a special loop-back plug is required as follows:
Ports 1, 2, 4 & 8 - RS-232 use a 9-pin female D-type loop-back plug (see Fig. 3-9).
Ports 3, 5 & 9 - RS-485 use a 9-pin female D-type loop-back plug (see Fig. 3-10).
This group of tests verifies the correct operation of the Communication Interface. COM1,
COM2, COM3, COM4, COM5, COM8 and COM9 can be tested with this diagnostic. The
ControlWave EFM communication port that is connected to the PC (local or network and
used for running these tests) can't be tested until diagnostics has been established via one
of the other ports, i.e., to test all ControlWave EFM communication ports (via WINDIAG),
communications with the PC will have to be established twice (each time via a different
port). It should be noted that the ControlWave EFM communication port that is connected
to the PC (RS-232, RS-485 or Ethernet) must be good for WINDIAG to run the
Communications Diagnostics
3.5.1.2 Serial Comm. Port External Loop-back Test Procedure
Connect an external loop-back plug to the CPU Port to be tested, i.e., J3 of CPU for COM1,
J4 of CPU for COM2 2, J5 of CPU for COM3, J1 of ECOM1 for COM4, J2 of ECOM1 for
COM5, J1 of ECOM2 for COM8 or J2 of ECOM2 for COM9 (see Figures 3-9 through 3-11).
3-14 / Service
Checks the CPU Module (except for RAM & PROM).
Checks the CPU's RAM and PROM hardware.
Checks Comm. Ports 1, 2, 3, 4, 5, 8 and 9 - The External
loop-back tests require the use of a loop-back plug.
Checks AOs on AI/O & Mixed I/O Modules.
Checks AIs on AI/O & Mixed I/O Modules.
Checks DIs or DOs on DI/O & Mixed I/O Modules.
Checks HSCs on HSC & Mixed I/O Modules.
CI-ControlWave EFM

Advertisement

loading

This manual is also suitable for:

Controlwave efm fgr09csuBristol controlwave efm