4.4 INPUT/OUTPUT MODULE SPECIFICATIONS

4.4.1 Non-isolated Analog Input/Output Module

Non-isolated Analog Inputs
Number of Inputs:
Input Type:
Input Impedance:
Non-isolated Analog Outputs
Number of Outputs:
4-20mA Output
Compliance:
1-5V Output:
General AI/AO Module Specs.
Accuracy:
4-4 / Specifications
Figure 4-2 - SCM - TB1 (Power Connector)
6 Single Ended Inputs (1-5V or 4-20Ma) individually
jumper configurable
(Externally Powered) Voltage Input: 1-5 Vdc
(Externally Powered) Current Loop: 4-20mA
1 Meg ohm for 1-5V inputs
250 ohm for 4-20mA inputs
2 AOs (1-5V or 4-20Ma) individually jumper configurable
250 ohm load with 11V External Power Source
650 ohm load with 24V External Power Source
5mA maximum output current into external load with
external voltage range of 11 to 30 Vdc
Analog Input
0.1% of Span @ +25ºC (+77ºF)
0.2% of Span @ -40ºC to +70ºC (-40ºF to 158ºF)
Analog Output
Current Output:
0.1% of Span @ +25ºC (+77ºF)
0.2% of Span @ -20ºC to +70ºC (-4ºF to 158ºF)
0.3% of Span @ -40ºC to +70ºC (-40ºF to 158ºF)
Voltage Output Compliance (I
(see Note
1
0.1% of Span + X @ +25ºC (+77ºF)
0.2% of Span + X @ -20ºC to +70ºC (-4ºF to +158ºF)
0.3% of Span + X @ -40ºC to +70ºC (-40ºF to 158ºF)
where X = [(2.5 ohms x I
Note
: Does not include error due to inductors
1
max = 5mA):
load
& Note
)
2
)/4.4V x 100]
load
CI-ControlWave EFM