Environmental Monitoring Probe (Fc 03 Or 04) - Eaton Power Xpert Gateway Series 1000 Card User Manual

Gateway series
Hide thumbs Also See for Power Xpert Gateway Series 1000 Card:
Table of Contents

Advertisement

MODBUS REGISTERS

Environmental Monitoring Probe (FC 03 or 04)

The optional Environmental Monitoring Probe for the PDU/RPP can
measure temperature and humidity. Because the device can be located
outside the PDU/RPP, the reference is to "auxiliary" data. In addition, it
contains two connections for monitoring the condition of auxiliary input
contacts, such as a door switch. See Table 9 for a list of EMP registers.
An exception code is returned if the EMP is not installed.
To read the temperature at the PDU/RPP, set the Modbus program to
Unit ID 254 and coil address 12028:
Table 9. Environmental Monitor (FC 03 or 04)
Name
Vendor Name
Model Name
Display Name
Serial Number
Device ID
Auxiliary Input 1
Auxiliary Input 2
Auxiliary Temperature
Auxiliary Humidity
68
EATON Power Xpert
IP: <IP address of PDU/RPP>
Unit ID: 254
Starting Register: 12028
Number of registers: 2
Function Code: 04
Register
1001
1033
1065
1123
1099
10275
10276
12028
12030
®
Gateway Series 1000 Card User's Guide
Data Type
STRING
STRING
STRING
STRING
UINT
UINT
UINT
FLOAT
FLOAT
S
164201670 Rev 1
Bytes
64
64
64
64
4
2
2
4
4