Table 3. PDU/RPP Registers (FC 04) (continued)
Name
I A out THD
I B out THD
I C out THD
VA in THD
VB in THD
VC in THD
VA in THD
VB in THD
VC in THD
CFph A out
CFph B out
CFph C out
Output Frequency
Input Frequency
Current Time

PDU/RPP Alarms (FC 02)

The PDU/RPP monitors the condition of several parameters and can
activate an alarm status if a parameter is out of range. For example, if
the input frequency is too high or too low, the PDU/RPP can set the
Input Frequency Fault Alarm.
To read the Input Frequency Fault Alarm, set the Modbus program to
Unit ID 1 and coil address 1008:
IP: <IP address of PDU>
Unit ID: 1
Starting Register: 1008
Number of Registers: 1
Function Code: 02
The PDU/RPP returns a single register that is a BOOL value (0 or 1),
indicating if the alarm is active or not active.
EATON Power Xpert
®
Gateway Series 1000 Card User's Guide
MODBUS REGISTERS
Register
Data Type
8014
FLOAT
8016
FLOAT
8018
FLOAT
8042
FLOAT
8044
FLOAT
8046
FLOAT
8048
FLOAT
8050
FLOAT
8052
FLOAT
8312
FLOAT
8314
FLOAT
8316
FLOAT
11002
FLOAT
11004
FLOAT
12203
TIME
S