MODBUS REGISTERS

PDU/RPP Registers and Alarms

This section contains information for the PDU/RPP Registers (FC 04) and
PDU/RPP Alarms (FC 02).

PDU/RPP Registers (FC 04)

To read the vendor name in the PDU/RPP, set the Modbus program to
Unit ID 1 and register 1001:
The PDU/RPP returns 32 registers containing up to 64 characters. There
are two ASCII characters per register, so the vendor name could be
displayed as POWERWARE.
Table 3. PDU/RPP Registers (FC 04)
Name
54
EATON Power Xpert
IP: <IP address of PDU/RPP>
Unit ID: 1
Starting Register: 1001
Number of registers: 32
Function Code: 04
Vendor Name
Model Name
Display Name
Device Type
Device ID
Device Guid
Serial Number
Conn Style
Device Comm Address
Device Baud Rate
Time Sync Period
Data Update Period
Device VAR Rating
Device Volts In Rating
Device Volts Out Rating
®
Gateway Series 1000 Card User's Guide
Register
Data Type
1001
STRING
1033
STRING
1065
STRING
1097
UINT
1099
UINT
1103
STRING
1123
STRING
1159
UINT
1160
STRING
1192
UINT
1194
UINT
1196
UINT
1198
UINT
1204
UINT
1206
UINT
S
164201670 Rev 1
Bytes
64
64
64
4
4
40
64
2
64
4
4
4
4
4
4