MODBUS REGISTERS

Breaker Data and Alarms

This section contains:
S
S
S

Breaker #1 Data Registers (FC 04)

To specify a specific breaker, use a Unit ID for breaker data along with
the register number for the specific breaker.
For example, "Watts in Phase A" is register 1055 for Breaker #1. This
statement is true for any panel. To specify a specific panel for breaker
data, use the panel's Unit ID in the Modbus program. For Panel #6
(Unit ID 23), the Modbus program would be set as follows:
The Modbus program would return a value of the watts in Phase A for
Breaker #1 in Panel #6 of the PDU/RPP at the specified IP address.
Table 7. Breaker #1 Data Registers (FC 04)
Name
64
EATON Power Xpert
Names of breaker parameters along with the register numbers for
Breaker #1
Instructions for calculating the register numbers for other breakers
Breaker alarms
IP: <IP address of PDU/RPP>
Unit ID: 23
Starting Register: 1055
Number of registers: 2
Function code: 04
Display Name
Number of Phases
Breaker Rating
Breaker Warning
Breaker Overload
AC Current Phase A
AC Current Phase B
AC Current Phase C
AC MAX Current Phase A
AC MAX Current Phase B
®
Gateway Series 1000 Card User's Guide
Register
Data Type
1000
STRING
1032
UINT
1033
UINT
1035
UINT
1036
UINT
1037
FLOAT
1039
FLOAT
1041
FLOAT
1043
FLOAT
1045
FLOAT
S
164201670 Rev 1
Bytes
64
2
4
2
2
4
4
4
4
4