Calculating Breaker Register Numbers - Eaton Power Xpert Gateway Series 1000 Card User Manual

Gateway series
Hide thumbs Also See for Power Xpert Gateway Series 1000 Card:
Table of Contents

Advertisement

MODBUS REGISTERS

Calculating Breaker Register Numbers

Table 7 shows the register numbers for Breaker #1. There can be many
breakers in a panel. Determine the corresponding register numbers for
other breakers in the panel by using the following formula:
Breaker register # = Breaker #1 register + ((Breaker # – 1) x 200))
For example:
Breaker #2 starts at 1200:
Breaker #3 starts at 1400:
Breaker #14 starts at 3600:
This formula works for any register. For example, for Breaker #1, the
register number of "Watts Phase A" is 1055. The corresponding
address for Breaker #18 is:
66
EATON Power Xpert
®
Gateway Series 1000 Card User's Guide
1000 + ((2 – 1) x 200)
1000 + (1 x 200)
1000 + 200
1200
1000 + ((3 – 1) x 200)
1000 + (2 x 200)
1000 + 400
1400
1000 + ((14 – 1) x 200)
1000 + (13 x 200)
1000 + 2600
3600
1055 + ((18 – 1) x 200)
1055 + (17 x 200)
1055 + 3400
4455