Accel/Decel Characteristics - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Accel/Decel
Characteristics
Set value
Curve
Output frequency
Accel
A97
Output frequency
Decel
A98
Linear acceleration
Typical
and deceleration for
applications
general-purpose use
"A" Function
Func.
Name
Code
A097 Acceleration curve
selection
A098 Deceleration curve
selection
Standard (default) acceleration and deceleration is linear with time. The inverter CPU can also
calculate other curves shown in the graphs below. The sigmoid, U-shape, and reverse U-shape
curves are useful for favoring the load characteristics in particular applications. Curve settings
for acceleration and deceleration are independently selected parameters A097 and A098
respectively. You can use the same or different curve types for acceleration and deceleration.
00
Linear
Output frequency
time
Output frequency
time
Avoid jerk on start/stop
for elevators; use for
delicate loads on con-
veyors
Description
Set the characteristic curve
of Accel1 and Accel2, four
options:
00 Linear
01 S-curve
02 U-shape
03 Reverse U-shape
Set the characteristic curve
of Decel1 and Decel2, four
options:
00 Linear
01 S-curve
02 U-shape
03 Reverse U-shape
01
02
Sigmoid
U-shape
Output frequency
time
Output frequency
time
Tension control for winding applications, web
presses, roller/accumulators
Defaults
Run
Mode
Edit
–FE2
–FU2
Lo Hi
(EU)
(US)
✘ ✘
00
00
✘ ✘
00
00
L300P Inverter
03
Reverse U-shape
Output frequency
time
Output frequency
time
SRW Display
Units
–FR
(JP)
00
>A097 ACCEL
LINE
Linear
00
>A098 DECEL
LINE
Linear
3–25
time
time