Ul Cautions, Warnings, And Instructions; Terminal Tightening Torque And Wire Size - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

xii
®
UL
Cautions, Warnings, and Instructions
Wiring Warnings
for Electrical
Practices and
Wire Sizes
Terminal Tighten-
ing Torque and
Wire Size
The Cautions, Warnings, and instructions in this section summarize the procedures necessary to
ensure an inverter installation complies with Underwriters Laboratories
WARNING: "Use 60/75°C Cu wire only" or equivalent.
WARNING: "Open Type Equipment." For models L300P–900H to L300P–1320H.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 240 V maximum." For models with suffix L.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 480 V maximum." For models with suffix H.
The wire size range and tightening torque for field wiring terminals are presented in the table
below.
Motor
Input
Output
Voltage
HP
kW
2
1.5
-015LFU2
3
2.2
-022LFU2
5
3.7
-037LFU2
7.5
5.5
-055LFU2
10
7.5
-075LFU2
15
11
-110LFU2
20
15
-150LFU2
200V
25
18.5
-185LFU2
30
22
-220LFU2
40
30
-300LFU2
50
37
-370LFU2
60
45
-450LFU2
75
55
-550LFU2
100
75
-750LFU2
Inverter Models,
Wire Size Range (AWG)
L300P
2/0 || 2/0 AWG
3/0 || 3/0 AWG
®
guidelines.
Torque
ft-lbs
14
1.1
14
1.1
10
1.1
8
1.8
6
1.8
4
3.6
2
3.6
1
3.6
1/0
6.5
1/0
6.5
1/0 || 1/0
6.5
1/0 || 1/0
10.1
10.1
10.1
N-m
1.5
1.5
1.5
2.5
2.5
4.9
4.9
4.9
8.8
8.8
8.8
13.7
13.7
13.7