Communications Protocol; Introduction To Command List - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Communications Protocol

Introduction to
The network master sends a frame to initiate
Command List
communications with a slave, as shown in the
figure to the right. After the set waiting time
(per parameter C078, the inverter responds.
The following table lists the commands, single-character codes sent to a particular device on
the network.
NOTE: Use of command 08 – set inverter parameters to default values first requires setting the
initialization mode parameter B084 to 01 (initializes parameters only) or 02 (initializes param-
eters and clears the trip history).
Command
Code
00
Forward / Reverse / Stop command
01
Setting of frequency in standard profile
02
Setting of intelligent terminal state
03
Read all monitor data (block read)
04
Read inverter status
05
Read trip history
06
Read a single parameter value
07
Write a single parameter value
08
Set inverter parameters to default values
09
Verifies that the requested setting can be
written to EEPROM.
0A
Writes a parameter value to EEPROM
0B
Requests the recalculation of internal constant
Host
(master)
Inverter
(slave)
Description
L300P Inverter
frame
wait
time
frame
User-selectable
B–5