Overload Restriction - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Overload
Restriction
"B" Function
Func.
Name
Code
B021 Overload restriction
operation mode
B022 Overload restriction
setting
B023 Deceleration rate at

overload restriction

B024 Overload restriction
operation mode (2)
B025 Overload restriction
setting (2)
If the inverter's output current exceeds a
preset current level you specify during
acceleration or constant speed, the
overload restriction feature automati-
cally reduces the output frequency to
restrict the overload. This feature does
not generate an alarm or trip event. You
can instruct the inverter to apply
overload restriction only during
constant speed, thus allowing higher
currents for acceleration. Or, you may
use the same threshold for both acceler-
ation and constant speed.
When the inverter detects an overload, it must decelerate the motor to reduce the current until it
is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower
the output current.
Description
Select the operating mode
during overload conditions,
three options, option codes:
00 Disabled
01 Enabled for acceleration
and constant speed
02 Enabled for constant
speed only
Sets the level for overload
restriction, between 50%
and 150% of the rated
current of the inverter,
setting resolution is 1% of
rated current
Sets the deceleration rate
when inverter detects
overload, range is 0.1 to
30.0, resolution is 0.1.
Select the operating mode
during motor overload
conditions, four options,
option codes:
00 Disabled
01 Enabled for acceleration
and constant speed
02 Enabled for constant
speed only
Sets the level for overload
restriction (2), between 50%
and 150% of the rated
current of the inverter,
setting resolution is 1% of
rated current
restriction area
Motor
Current
0
Output
Frequency
B023
Defaults
Run
Mode
Edit
–FE2
–FU2
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✔
01
01
01
✘ ✔
rated
rated
rated
cur-
cur-
cur-
rent
rent
rent
times
times
times
1.20
1.10
1.20
✘ ✔
1.00
15.0
1.00
✘ ✔
01
01
01
✘ ✔
rated current times
1.20
3–33
L300P Inverter
B022
t
t
Units
SRW Display
>b021 OLOAD
1MODE
ON
A
>b022 OLOAD
1LEVEL
0024.8A
sec.
>b023 OLOAD
1CONST
01.00
>b024 OLOAD
2MODE
ON
A
>b025 OLOAD
2LEVEL
0024.8A