Terminal Dimensions And Torque Specs - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

2–16
Step-by-Step Basic Installation
Terminal
Dimensions and
Torque Specs
Voltage
The following tables list the screw size of terminal and recommended torque for tightening for
each of the L300P inverter models (400V models are on the next page).
CAUTION: Fasten the screws with the specified fastening torque in the table below. Check for
any loosening of screws. Otherwise, there is the danger of fire.
Motor
200V
Output
Inverter
Input
Models,
HP
kW
L300P
2
1.5
–015LFU2
3
2.2
–022LFU2
5
3.7
–037LFU2
7.5
5.5
–055LFU2
10
7.5
–075LFU2
15
11
-110LFU2
20
15
-150LFU2
200V
25
18.5
-185LFU2
30
22
-220LFU2
40
30
-300LFU2
50
37
-370LFU2
60
45
-450LFU2
75
55
-550LFU2
100
75
-750LFU2
Note 1: The recommended ring lug connector listing consists of wire size – screw size
format. The wire sizes are in AWG or mm
for the ring lug centers are: #10, #12, 1/4", 5/16", and 1/2". For metric wire sizes, bolt
sizes for the ring lug centers are: 6 = 6M, 8 = 8M, 10 = 10M
TIP: AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
kcmil = 1,000 circular mils, a measure of wire cross-sectional area
2
mm
= square millimeters, a measure of wire cross-sectional area
Ring Lug Connector *1
Screw size
of terminal
(AWG–bolt)
M4
14–#10
M4
14–#10
M4
10–#10
M5
8–#12
M5
6–#12
M6
4–1/4
M6
2–1/4
M6
1
M8
1–5/16
M8
2–5/16
M8
2–5/16
M10
1–1/2
M10
2/0–1/2
M10
3/0–1/2
2
format. For AWG wire sizes, bolt sizes
Torque
2
ft-lbs
N-m
(mm
–bolt)
2–4
1.1
1.5
2–4
1.1
1.5
3.5–4
1.1
1.5
5.5–5
1.8
2.5
8–5
1.8
2.5
14–6
3.6
4.9
22–6
3.6
4.9
30–6
3.6
4.9
38–8
6.5
8.8
60–8
6.5
8.8
100–8
6.5
8.8
100–10
10.1
13.7
150–10
10.1
13.7
150–10
10.1
13.7

Advertisement