Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output relay contacts are
closed when the inverter is in Run Mode
(normally open logic).
Opt.
Symbol
Function Name
Code
00
RUN
Run signal
11, 12, AL0 – AL2
Valid for
outputs:
(none)
Required
settings:
Notes:
• The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082. The
start frequency is the initial inverter output
frequency when it turns ON.
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter's
output transistor.
[FW, RV]
Motor
speed
start freq.
B82
Run
Signal
Output
Description
State
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example: (Default output configuration
shown—see page 3–48.)
Inverter output terminal circuit
RUN
12C
12A
24VDC
+
L
See I/O specs on page 4–8.
t
11C
11A