L300P Dynamic Braking Selection Tables - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

L300P
The L300P Series 200V and 400V class inverter models in the 2 to 20 hp range have internal
braking units. Additional stopping torque is available by adding external resistors. The required
Dynamic Braking
braking torque depends on your particular application. Other tables in this section will help you
Selection Tables
choose the proper resistor.
2 to 20 hp (1.5 to 15 kW)
Voltage
Model Number,
Class
L300P
–015LFU2
–022LFU2
–037LFU2
200V
–055LFU2
–075LFU2
–110LFU2
–150LFU2
–015HFU2, HFE2
–022HFU2, HFE2
–037HFU2, HFE2
400V
–055HFU2, HFE2
–075HFU2, HFE2
–110HFU2, HFE2
–150HFU2, HFE2
Without
External Resistor
Braking
Motor
Braking
Torque
hp
Unit
@ 60Hz,
%
2
Built-in
50
3
Built-in
20
5
Built-in
20
7.5
Built-in
20
10
Built-in
20
15
Built-in
10
20
Built-in
10
2
Built-in
50
3
Built-in
20
5
Built-in
20
7.5
Built-in
20
10
Built-in
20
15
Built-in
10
20
Built-in
10
Using Optional
External Resistor
Minimum Resistance
Braking
External
Minimum
Torque
Resistance,
Resistance,
@60Hz,
Ohms
Ohms
%
35
200
35
160
35
100
17
80
17
80
17
55
17
50
100
200
100
200
100
140
70
100
70
100
70
55
70
50
L300P Inverter
Performance @
Minimum
Resistance
@ 100%
Max.
Braking
Braking
Duty
Duty
Cycle,
Cycle,
Ohms
%
35
10
100
35
10
100
35
10
100
17
10
50
17
10
50
17
10
50
17
10
50
100
10
300
100
10
300
70
10
200
70
10
200
50
10
150
50
10
150
50
10
150
5–7

Advertisement