Avaya IP600 Overview page 19

Internet protocol communications server
Hide thumbs Also See for IP600:
Table of Contents

Advertisement

Hardware
Table 1.
Cabinet Power Source Information
Cabinet Style and Power
Distribution Unit
Rack Mount Cabinet. AC power
supply (650A integrated power
supply)
1
There is no integrated DC power supply. DC rectifiers can be used if desired; follow manufacturer's instructions.
Overview for Avaya IP600 Internet Protocol Communications Server
555-233-001 — Issue 5 — November 2000
The Avaya IP600 should be installed in a well-ventilated area. Maximum equipment
performance is achieved at an ambient temperature between 40 and 120 °F (4 and
49 °C) for a short-term operation (not more than 72 consecutive hours or 15 days in a
year) and up to 110 °F (43 °C) for a continuous operation.
The relative humidity range is 10% to 95% at up to 84 °F (29 °C). Above this,
maximum relative humidity decreases from 95% down to 32% at 120 °F (49 °C).
Installations outside these limits may reduce system life or affect operation. The
recommended temperature and humidity range is 65 to 85 °F (18 to 29 °C) at 20% to
60% relative humidity.
The other Environmental Considerations and System Protection requirements
described in the DEFINITY ECS Systems Description under "Site Requirements"
apply to the Avaya IP600 as well.
1
Power Sources
Single phase 120 VAC with neutral
Single phase 240 VAC with neutral
Table 2.
Circuit Breakers for AC-Powered Cabinets
Cabinet Type
Rack Mount Cabinet (120 VAC) 60 Hz
Rack Mount Cabinet (240 VAC) 50 Hz
Power Input Receptacles
120 VAC, 60 Hz NEMA 5-15R
240 VAC, 50 Hz IEC 320
Japan installations use country
specific receptacles for 100 and
200 VAC, 50/60 Hz
Circuit Breaker Size
15 A
10 A
1
7