E: Motor Parameters - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

B.2 Parameter Table
No.
Name
Analog Frequency
d4-07
Reference Fluctuation
<22>
Limit (Up/Down 2)
d4-08
Frequency Reference Bias
<22>
Upper Limit (Up/Down 2)
d4-09
Frequency Reference Bias
<22>
Lower Limit (Up/Down 2)
Up/Down Frequency
d4-10
Reference Limit Selection
Bi-Directional Output
d4-11
Selection
d4-12
Stop Position Gain
d7-01
Offset Frequency 1
<22>
d7-02
Offset Frequency 2
<22>
d7-03
Offset Frequency 3
<22>
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<19> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<22> Parameter can be changed during run.
u

E: Motor Parameters

No.
Name
This parameter must be set to the power supply voltage. It
sets the maximum and base voltage used by preset V/f
patterns (E1-03 = 0 to E) and adjusts levels used by certain
E1-01
Input Voltage
functions.
<24>
Setting
WARNING! Drive input voltage (not motor voltage) must
be set in E1-01 for the protective features of the drive to
function properly. failure to do so may result in equipment
damage and/or death or personal injury.
Selects a preset V/f pattern.
0: 50 Hz Constant torque 1
1: 60 Hz Constant torque 2
2: 60 Hz Constant torque 3 (50 Hz base)
3: 72 Hz Constant torque 4 (60 Hz base)
4: 50 Hz Variable torque 1
5: 50 Hz Variable torque 2
6: 60 Hz Variable torque 3
V/f Pattern
7: 60 Hz Variable torque 4
E1-03
Selection
8: 50 Hz High starting torque 1
9: 50 Hz High starting torque 2
A: 60 Hz High starting torque 3
B: 60 Hz High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f. E1-04 through E1-13 settings define the V/
f pattern.
308
Description
When an Up 2 or Down 2 input is active and the frequency
reference value from analog or pulse input changes for more
than the level set in d4-07, the bias value is hold and the
frequency reference is changed to the new value.
After the speed reaches the frequency reference the bias hold
is released.
Sets the upper limit for the bias and the value that can be saved
in d4-06. Set as a percentage of the maximum output frequency
E1-04.
Sets the lower limit for the bias and the value that can be saved
in d4-06. Set as a percentage of the maximum output frequency
E1-04.
Selects which value is used as frequency reference lower limit
if the Up/Down function is used.
0: The lower limit is determined by d2-02 or analog input
(H3-02/10 = 0). The higher of both values becomes the
reference limit.
1: The lower limit is determined by d2-02.
Enables or disables conversion of frequency reference or PID
output value into bi-directional internal frequency reference.
0: Disabled - 0 to 100% reference or PID output: Operation in
selected direction
1: Enabled - freq. ref. or PID output < 50%: Reverse operation;
freq. ref. or PID output > 50%: Operation in selected direction
Sets the gain used by the simple positioning stop function to
fine adjust the position.
d7: Offset Frequency
Use d7 parameters to set the offset frequency.
Added to the frequency reference when the digital input
"Frequency Offset 1" (H1- = 44) is switched on.
Added to the frequency reference when the digital input
"Frequency Offset 2" (H1- = 45) is switched on.
Added to the frequency reference when the digital input
"Frequency Offset 3" (H1- = 46) is switched on.
Description
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
Control
Mode
Range
Def.
V/f
0.1 to
1.0% A A A
+100.0
0.1 to
0.0% A A A
100.0
-99.9 to
0.0% A A A
0.0
0 or 1
0
A A A
0 or 1
0
A A A
0.50 to
1.00 A A A
2.55
-100.0 to
0.0% A A A
+100.0
-100.0 to
0.0% A A A
+100.0
-100.0 to
0.0% A A A
+100.0
Control
Mode
Range
Def.
V/f OL
V
155 to 255
200 V
S
S
0 to F
F
A
A
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Addr.
Pg.
Hex
O
P
LV
M
2AE
141
2AF
141
2B0
141
2B6
141
2B7
142
2B8
142
2B2
142
2B3
142
2B4
142
Addr. Hex Pg.
PM
S
300
144
302
144

Hide quick links: