Advertisement

Set as a percentage of the maximum output frequency.
Note: The lower limits for the Jog frequency, multi-step speed settings, and 2-step speed settings do not change. When lower limits are set to
both the frequency reference (d2-02) and the main frequency reference (d2-03), the drive uses the greater of those two values as the lower
limit.
No.
d2-03
u

d3: Jump Frequency

n
d3-01 to d3-04: Jump Frequencies 1, 2, 3 and Jump Frequency Width
In order to avoid continuous operation at a speed that causes resonance in driven machinery, the drive can be programmed
with three separate Jump frequencies that will not allow continued operation within specific frequency ranges. If the speed
reference falls within a Jump frequency dead band, the drive will clamp the frequency reference just below the dead band
and only accelerate past it when the frequency reference rises above the upper end of the dead band.
Setting parameters d3-01 through d3-03 to 0.0 Hz disables the Jump frequency function.
No.
d3-01
d3-02
d3-03
d3-04
Figure 5.33
shows the relationship between the Jump frequency and the output frequency.
Note: 1. The drive will use the active accel/decel time to pass through the specified dead band range but will not allow continuous operation
in that range.
2. When using more than one Jump frequency, make sure that d3-01 ≥ d3-02 ≥ d3-03.
u

d4: Frequency Hold and Up/Down 2 Function

n
d4-01: Frequency Reference Hold Function Selection
This parameter is effective when either of the digital input functions listed below is used.
• Accel/decel ramp hold function (H1-= A)
• Up/Down function (H1- = 10 and 11, sets the frequency reference by digital inputs)
• Up/Down 2 function (H1- = 75/76, adds a bias to the frequency reference using digital inputs)
Parameter d4-01 determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the
Run command is cleared or the power supply is shut down.
No.
d4-01
Frequency Reference Hold Function Selection
The operation depends on with what function parameter d4-01 is used.
Setting 0: Disabled
• Acceleration Hold
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Parameter Name
Master Speed Reference Lower Limit
Parameter Name
Jump Frequency 1
Jump Frequency 2
Jump Frequency 3
Jump Frequency Width
Output
frequency
Frequency
reference
decreases
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Figure 5.33 Jump Frequency Operation
Parameter Name
Setting Range
0.0 to 110.0%
Setting Range
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 20.0 Hz
Frequency
reference
increases
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Jump
Jump
Frequency 2
Frequency 1
d3-02
d3-01
Setting Range
5.4 d: Reference Settings
Default
0.0%
Default
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
Frequency
reference
Default
0 or 1
0
5
137