3.7 Control Circuit Wiring

3.7

Control Circuit Wiring

NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
Main speed
frequency
reference.
Multi-function
programmable
Safe Disable
Input
<1> Connected using sequence input signal (S1 to S6) from NPN transistor; Default: sink mode (0 V com)
<2> Use only the +24 V internal power supply in sinking mode; the source mode requires an external power supply.
to I/O Connections on page
u

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S6), multi-function digital
outputs (MA, MB), multi-function pulse inputs and outputs (RP, MP) and multi-function photocoupler outputs (P1, P2).
The default is called out next to each terminal in
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive
with untested control circuits could result in death or serious injury.
50
<1>
Forward run/stop
S1
S2
Reverse run/stop
S3
External fault
Fault reset
S4
Multi-step
speed 1
S5
main/aux switch
Multi-step
speed 2
S6
<2>
Digital inputs
(default setting)
DIP
switch S3
SC
Shield ground
terminal
Pulse train input
R
P
(max. 32 kHz)
Setting power supply
+V
+10.5 max. 20 mA
2 k
A1
0 to +10 V (20 k )
A2
0 to +10 V (20 k )
(0)4 to 20 mA (250
AC
Safety switch
H2
H1
Jumper
HC
shielded line
main circuit terminal
Figure 3.14 Control Circuit Connection Diagram
55.
Figure
V1000
Control circuit
Option card
connector
DIP switch S1
V
I
+ 24 V 8 mA
MA
MB
24 V
MC
Sink
Source
P1
0 V
P2
PC
MP
AM
)
AC
Termination
DIP
resistor
switch
120
, 1/2 W
, 1/2 W
S2
R +
R -
S +
S -
IG
Cable shield ground
twisted-pair shielded line
control terminal
3.14.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)
Digital output
Fault
5 ~ 48 Vdc
2 to 50 mA
(default setting)
During Run
(photocoupler 1)
Frequency agree
(photocoupler 2)
Photocoupler
output common
Pulse train output
0 to 32 kHz
Analog monitor
+
output
AM
0 to +10 Vdc
(2 mA)
-
Comm.
Monitor
connector
output
MEMOBUS/
Modbus comm.
RS-485/422
Refer