C4: Torque Compensation - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

5.3 C: Tuning
No.
C3-02
Note: When using V/f Control (A1-02 = 0), the default setting becomes 2000 ms. When using Open Loop Vector Control (A1-02 = 2), the default
setting becomes 200 ms. This function is not available when using V/f Control with Simple PG Feedback.
n
C3-03: Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).
No.
C3-03
The slip compensation limit is constant throughout the constant torque range. In the constant power range it is increased
based on C3-03 and the output frequency as shown in the following diagram.
Note: This parameter is disabled when using V/f Control with Simple PG Feedback Control (H6-01 = 3).
n
C3-04: Slip Compensation Selection during Regeneration
When the slip compensation during regeneration function has been activated and regenerative load is applied, it might be
necessary to use a braking option (braking resistor, braking resistor unit, or braking unit).
Even if enabled, this function does not operate when the output frequency is too low.
No.
C3-04
Slip Compensation Selection during Regeneration
Setting 0: Disabled
Slip compensation is not provided. Depending on the load and operation mode (motoring or regenerative) the actual motor
speed will be lower or higher than the frequency reference.
Setting 1: Enabled
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
n
C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
No.
C3-05
Setting 0: Disabled
Setting 1: Enabled
u

C4: Torque Compensation

The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.
Note: Before making changes to the torque compensation parameters make sure the motor parameters and V/f pattern are set properly or perform
Auto-Tuning.
n
C4-01: Torque Compensation Gain
Sets the gain for the torque compensation function.
No.
C4-01
128
Parameter Name
Slip Compensation Primary Delay Time
Parameter Name
Slip Compensation Limit
E1-04
E1-06 × C3-03
C3-03
Figure 5.26 Slip Compensation Limit
Parameter Name
Parameter Name
Output Voltage Limit Operation Selection
Parameter Name
Torque Compensation Gain
output frequency
E1-06
E1-04
Base
Maximum
Frequency
Frequency
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Setting Range
Determined by
0 to 10000 ms
Setting Range
0 to 250%
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
Determined by
0.00 to 2.50
Default
A1-02
Default
200%
Default
0
Default
0
Default
A1-02