Single/Three-Phase 200 V Class Drive; Single/Three-Phase 200 V Class Drive - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

A.2 Single/Three-Phase 200 V Class Drive
Three-Phase: VZA
Single-Phase: VZA
Maximum Motor Size Allowed (kW)
Input
Input Current (A)
Rated Output Capacity (kVA)
Output Current (A)
Output
Overload Tolerance
Max Output Voltage (V)
Max Output Frequency (Hz)
Power
Supply
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Harmonic Corrective Actions
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor.
<2> This drive does not have a Normal Duty rating.
<3> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor rated current.
<4> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<5> Rated motor capacity is calculated with a rated output voltage of 220 V.
<6> Carrier frequency is set to Swing PWM. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<8> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Table A.2 Power Ratings
Item
<1>
HD Rating
<3>
ND Rating
HD Rating
Three-Phase
ND Rating
<4>
HD Rating
Single-Phase
ND Rating
HD Rating
<5>
ND Rating
HD Rating
ND Rating
Carrier Frequency
Rated Voltage
Rated Frequency
DC Reactor
A.2 Single/Three-Phase 200 V Class Drive
20P1
20P2
20P4
B0P1
B0P2
B0P4
0.1
0.2
0.4
0.2
0.4
0.75
0.7
1.5
2.9
1.1
1.9
3.9
1.4
2.8
5.5
2.0
3.6
7.3
0.3
0.6
1.1
0.5
0.7
1.3
<7>
<7>
0.8
1.6
3.0
<6>
1.2
1.9
3.5 (3.3)
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
User adjustable between 2 and 15 kHz (see HD output current line of this
table for default values)
Three-phase 200 to 240 V (proportional to input voltage)
400 Hz (user-adjustable)
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
Specification
20P7
21P5
22P2
B0P7
B1P5
B2P2
0.75
1.5
2.2
1.1
2.2
3.0
5.8
7.5
11.0
7.3
10.8
13.9
11.0
14.1
20.6
13.8
20.2
24.0
1.9
3.0
4.2
2.3
3.7
4.6
<7>
<7>
<8>
5.0
8.0
11.0
6.0
9.6
12.0
-15 to 10%
±5%
Optional
24P0
B4P0
<2>
4.0
<2>
5.5
18.9
24.0
35.0
6.7
7.5
<8>
<8>
17.5
19.6
A
289

Hide quick links:

Advertisement

Table of Contents
loading