H3: Multi-Function Analog Input Terminals - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Setting 3C: LOCAL/REMOTE Status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Open
REMOTE: The selected external reference (b1-01/02 or b1-15/16) is used as frequency reference and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Speed Search function.
Setting 3E: PID Feedback Low
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14.
Setting 3F: PID Feedback High
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the
level set to b5-36 for longer than the time set to b5-37.
Setting 4A: During KEB Operation
Output terminal closes while KEB is being performed.
for a KEB function description.
Setting 4B: During Short Circuit Braking
Closes the output terminal while Short Circuit Braking is being executed.
Setting 4C: During Fast-stop
Output terminal closes when a Fast-stop is being executed.
Setting 4D: oH Pre-Alarm Time Limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after ten frequency reduction operation cycles.
Selection on page 203
for details.
Setting 90 to 92: FBDs Digital Output 1 to 3
These settings are for digital output functions used by FBDs. Normally there is no need to change or apply these settings.
Setting 100 to 192 : Reverse Switching for Functions 0 to 92
These settings reverse the switching status of the specified function. Set as 1, where the last two digits specify the
setting number of the function to be reversed.
Examples:
• To reverse the output for "8: During Baseblock", set "108".
• To reverse the output for "4A: During KEB" set "14A" .
n
H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01/02/03 = 39), parameter H2-06
determines the units for the output signal.
The output is intended to drive a watt hour meter or a PLC input by a 200 ms pulse signal. A pulse is output according to
the kWh unit selected in H2-06.
No.
H2-06
u

H3: Multi-Function Analog Input Terminals

The drive is equipped with 2 multi-function analog input terminals, A1 and A2. The user can assign functions to these
terminals by setting parameters H3-02 and H3-10 between 0 and 31.
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Refer to PID Feedback Loss Detection on page 119
Refer to PID Feedback Loss Detection on page 119
Refer to Kinetic Energy Backup (KEB) Function on page 189
Parameter Name
Watt Hour Output Unit Selection
Description
Refer to b3: Speed Search on page 110
C1-09: Fast-stop Time
for details.
Refer to L8-03: Overheat Pre-Alarm Operation
Setting Range
0: 0.1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
5.7 H: Terminal Functions
for details on the
for details.
for details.
Default
1: 1 kWh units
5
0
177