H2: Multi-Function Output - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Setting 7C/7D: Short Circuit Braking (N.O./N.C.) (PM OLV only)
An input programmed for this function can be used to activate Short Circuit Braking in Open Loop Vector Control for PM
motors. By linking all three phases of a PM motor it creates a braking torque in a rotating motor and can be used to stop
a rotating motor or prevent a motor from coasting by external forces (like windmill effect in fan applications etc.).
Description
Normal operation
Short-Circuit Braking
Setting 7E: Forward Reverse Detection (V/f Control with Simple PG Feedback)
When a digital input is programmed for this function, the input determines the direction of the speed feedback signal for
V/f Control with PG feedback. If the input is open, the speed feedback signal is considered to be forward, if the input is
closed, it is considered to be in reverse.
Setting 7F: Bi-Directional PID Output Selection
If PID output to bi-directional output conversion is enabled in parameter d4-11, a digital input programmed for 7F can be
used to switch between normal output or bi-directional output.
If the digital input is open, the PID output builds the output frequency reference. If the input is closed, the PID output is
converted to bi-directional output frequency reference.
Setting 90 to 96: FBDs Digital Input 1 to 6
These settings are for digital inputs functions used by FBDs. Normally there is no need to change or apply these settings.
Setting 9F: FBDs Function Disable
This function is used to enable or disable a FBDs program in the drive. An input programmed for this function is effective
only if A1-07 = 2.
Status
Open
Closed
u

H2: Multi-Function Output

n
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 between 0 and 192 to assign functions
to these terminals. Default values are listed in the following table.
No.
H2-01
Terminal MA, MB and MC Function Selection (relay)
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
Note: If not using an input terminal or if using it in the through-mode, be sure to set that terminal to "F".
Setting
Function
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
D
Braking Resistor Fault
E
Fault
F
Not used/Through Mode
10
Alarm
11
Reset Command Active
12
Timer Output
13
Speed Agree 2
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Setting 7C (N.O.)
Open
Closed
Refer to C5: Automatic Speed Regulator (ASR) on page 129
Refer to d4-11: Bi-Directional Output Selection on page
Parameter Name
Table 5.27 Multi-Function Output Terminal Settings
Page
Setting
170
170
170
171
171
172
172
172
172
173
173
173
173
173
173
173
173
173
173
173
Digital Inputs
Description
FBDs enabled
FBDs disabled
Setting Range
0 to 192
0 to 192
0 to 192
Function
19
Torque Detection 2 (N.C.)
1A
During Reverse Operation
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre alarm (oH)
22
Mechanical Weakening
30
During Torque Limit
37
During Frequency Output
38
Drive Enable
39
Watt Hour Pulse Output
3C
LOCAL/REMOTE Status
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4A
During KEB Operation
4B
During Short-Circuit Braking
4C
During Fast-stop
4D
oH Pre-Alarm Time Limit
5.7 H: Terminal Functions
Setting 7D (N.C.)
Closed
Open
for details.
142.
Default
E: Fault
0: During Run
2: Speed Agree 1
Page
173
175
176
176
176
176
176
176
176
176
176
176
177
177
177
177
177
177
177
177
5
169

Hide quick links:

Advertisement

Table of Contents
loading