Unit Setting Methods - Omron NS - SETUP Setup Manual

Ns-series programmable terminals
Hide thumbs Also See for NS - SETUP:
Table of Contents

Advertisement

4-3-1

Unit Setting Methods

The methods for setting each Unit are as follows:
Connecting a CS-series CPU Unit
When a CS-series CPU Unit is connected, settings are required in the PLC Setup and on the
front-panel switches of the CPU Unit.
PLC Setup
There are two methods that can be used to change the parameters in the PLC Setup.
• CX-Programmer
• Programming Console
Using the CX-Programmer
Precautions
for Safe Use
1. Open the project file in the CX-Programmer and select PLC - PLC Information - PLC
Settings from the menus.
2. The PLC Settings Dialog Box will be displayed. Click the tab for the port to which the PT
is connected and change the following three parameters. (The following screen capture
is provided as an example. The parameters that are actually displayed will depend on
the model of the CPU Unit and the port.)
Item
Baud
Mode
NT/PLC
Link Max.
If one or more parameters in the PLC Setup in the CPU Unit has been previ-
ously changed, always upload the PLC Setup from the CPU Unit and make any
new changes in the uploaded copy so that you do not overwrite the previous
changes.
Select the Custom Option and set the baud rate to 115,200 bps (High-speed
1:N NT Link Mode). The format does not need to be changed.
Set the mode to the 1:N NT Link Mode.
If only one PT is connected to the port and it has a unit number of 0, set this
parameter to 1. Otherwise, set the highest unit number of all the PTs that are
connected.
4-3 High-speed 1:N NT Link
Description
4-19