4-2 1:N Host Connection
Item
Baud
Mode
NT/PLC
Link Max.
Using a Programming Console (CJ1 CPU Units Only)
If the PT is connected to the Host Link port (RS-232C port), connect the Programming Con-
sole to the CPU Unit and set the following values at the specified addresses of the PLC
Setup.
PLC
Setup
address
160
161
166
Reference
4-12
Select the Custom Option and set the baud rate to 38,400 bps (Standard 1:N
NT Link Mode). The format does not need to be changed.
Set the mode to the 1:N NT Link Mode.
If only one PT is connected to the port and it has a unit number of 0, set this
parameter to 1. Otherwise, set the highest unit number of all the PTs that are
connected.
Setting to write
8200 hex
Specifies using the Host Link port in 1:N NT Link Mode.
0000 to 0009 hex
Specifies the standard communications speed (38,400
bps). It does not matter what value between 0000 and
0009 is set.
If only one PT is connected to the port and it has a unit
000@ hex
number of 0, replace the box at the left with 1. Otherwise,
replace the box with the highest unit number of all the PTs
that are connected.
If the PT is connected to the peripheral port of the CPU Unit, make the above settings in
words 144, 145, and 150 of the PLC Setup instead of 160, 161, 166.
Description
Description