GRT1-PNT Unit components
DIP Switch 3: ADR
DIP Switch 4: BACK
20
When DIP switch 1 is ON (registered table enabled) and DIP switch 3 is
switched to ON, parameter data is automatically restored to the SmartSlice
I/O Units that had parameter data backed up.
/i
Switch 3 ADR
OFF
OFF to ON
When DIP switch 1 is ON (registered table enabled) and DIP switch 4 is turned
OFF to ON, the parameter data of all connected SmartSlice I/O Units is
backed up in the Communication Unit.
/i
Switch 4 BACK
ON
OFF
The backup operation starts after DIP switch 4 is
turned from ON to OFF to ON within 3 seconds.
Function
Automatic restore function disabled.
Automatic restore function enabled (when pin 1 is ON).
Function
Switch ON to OFF to ON to start the parameter backup (when
DIP switch 1 is ON).
---
max 3 s
ON
OFF
Section 2-1