GRT1-PNT Unit components
Status indicator
specification
Indicator
Colour
RUN
Green
Unit status
ERR
Red
Unit error
BF
Red
PROFINET IO
failure
TS
---
SmartSlice I/O
system
communication
Green
status
Red
UNIT PWR
Green
I/O PWR
Green
18
/i
Status
Meaning
Not lit
•
Start-up test failed, unit not operational.
•
Fatal error: Operation stopped.
Lit
Initialization successful, unit is in normal operation.
Not lit
Unit is in normal operation.
Flashing
A start-up error has occurred.
Lit
Fatal error in system execution.
Not lit
•
No PROFINET IO communication errors occurred.
•
I/O data exchange in progress.
Flashing
The configuration settings sent by the PROFINET IO Controller unit are
invalid. No I/O data exchange is possible.
Lit
No PROFINET IO communication has been detected by the unit.
Not lit
•
No power supplied.
•
Communication has not started with SmartSlice I/O Unit.
•
Over current detected.
Flashing once
SmartSlice I/O Unit added to the system
per second
Flashing twice
Backup/Restore function operating:
per second
•
Restoring settings to SmartSlice I/O Unit, backup function operating.
•
Downloading SmartSlice I/O Unit settings.
Lit
Communication with SmartSlice I/O Unit established.
Flashing
Non-fatal communication error occurred:
•
Communication time out.
•
Verification error occurred with registered table.
•
Different model Unit detected after SmartSlice I/O Unit replacement.
Lit for 2
Failure occurred while restoring settings to SmartSlice I/O Unit or
seconds
downloading SmartSlice I/O Unit settings.
Lit
Fatal communication error occurred.
Not lit
Power supply to the Unit is not present (All other LED indicators are also
OFF).
Lit
Power supply to the Unit is present.
Not lit
Power supply to the SmartSlice I/O Unit is not present. The SmartSlice I/O
Units may be operative, but no output is available.
Lit
Power supply to the SmartSlice I/O Unit is present.
RUN
RUN
UNIT PWR
UNIT PWR
ERR
ERR
BF BF
TS TS
I/O PWR
I/O PWR
Figure 2.1.4: GRT1-PNT LED indicators
Section 2-1