GRT1-PNT Unit components
Link activity specification
Indicator
Colour
LINK
Green
2-1-5
DIP switches
DIP Switch 1: REGS
DIP Switch 2: NC
/i
Status
Meaning
Not lit
No ethernet communication on corresponding port.
Lit
Transmission/reception is in progress with connected switch/IO Controller
for corresponding port.
Four DIP switches on the front of the Communication Unit are provided for
operational settings. The factory setting is OFF for all DIP switches.
/i
DIP Switch
1
2
3
4
Note
It is recommended to use the features that are made available by DIP switches 1, 3 and
4 (as discussed on the next page).
If DIP switch 1 is turned from OFF to ON while the Unit's power is ON, the
existing SmartSlice I/O Unit configuration (connection order and I/O size) is
registered in the PROFINET IO Communication Unit as a registered table.
If DIP switch 1 is ON when the Unit's power is turned ON, the actual
SmartSlice I/O Unit configuration at start-up is automatically compared to the
registered table. Any SmartSlice I/O Unit that does not match the registered
table will not participate in SmartSlice I/O communication.
/i
Switch 1 REGS
ON
OFF
OFF to ON
ON to OFF
DIP switch 2, marked NC, is not used and should always be set to OFF.
ON
Figure 2.1.5: GRT1-PNT DIP switches
Caption
Description
REGS
Create / Enable Registration Table
NC
Not Used (Always OFF)
ADR
Automatic Restore
BACK
Backup Trigger
Function
Registered table is enabled: if there is a verification error, the
affected Unit will not participate in communication.
Registered table is disabled: all Units always participate in
communication.
Register I/O Unit table
(Unit Power must be ON)
Clear registered I/O Unit table
(Unit Power must be ON)
1
REGS
NC
2
ADR
3
4
BACK
Section 2-1
19