Service Code
Data
Error Codes
94
For normal completion, the value when the left-most bit of the service code
specified in the command turns ON is stored as shown in the following table.
/i
Function
Command service code
Write data
10 Hex
Read data
0E Hex
Reset
05 Hex
Save
16 Hex
When an error response is returned for an explicit message, the value is
always 94 Hex.
Read data is included only when a read command is executed.
The explicit message error codes as listed in the following table.
/i
Response
Error name
code
08FF
Service not supported
09FF
Invalid Attribute value
16FF
Object does not exist
15FF
Too much data
13FF
Not enough data
0CFF
Object state conflict
20FF
Invalid parameter
0EFF
Attribute not settable
10FF
Device state conflict
14FF
Attribute not supported
19FF
Store operation failure
2AFF
Group 2 only server
general failure
Response service code
90 Hex
8E Hex
85 Hex
96 Hex
Cause
The Service code is incorrect.
The specified Attribute value is not supported.
The data written was outside valid range.
The specified Instance ID is not supported.
The data is larger than the specified size.
The data is smaller than the specified size.
The specified command cannot be executed
due to an internal error.
The specified operation command data is not
supported.
An Attribute ID supported only for reading has
been executed for a write service code.
The specified command cannot be executed
due to an internal error.
The specified Attribute is not supported.
The data cannot be stored in memory.
The specified command or Attribute is not
supported or the Attribute was not set.