GRT1-PNT Unit components
2-1-3
Field Ground Terminal
Recommended Wire
Strip Length
Pin Terminal Length
2-1-4
LED indicators
The following standards and specifications apply to the connectors for the
Ethernet twisted-pair cable.
Electrical specifications: Conforming to IEEE 802.3 standards
Shielded twisted-pair (STP) cable: minimum category CAT5
Connector structure: RJ45 8-pin Modular Connector (conforming to
ISO 877)
The GRT1-PNT PROFINET IO Communication Unit provides a Field gGround
Terminal at the front side.
Figure 2.1.3: GRT1-PNT Field Ground Terminal
To help prevent electrical shock and/or if noise is a significant source of errors,
ground the Field Ground Terminal with a ground resistance of less than 100 Ω
using a 14-gauge wire (minimum cross-sectional area of 2 mm
/i
Type
Stranded wire
Pin terminal
Strip wire between 8 mm and 10 mm of insulation at the ends of the wires
(stranded or solid wire) or use pin terminals with a pin (conductor) length of
8 mm to 10 mm.
Strip 8 to 10 mm.
The GRT1-PNT PROFINET IO Communication Unit uses the following LED
indicators.
Six LEDs to indicate status of the Unit and the PROFINET IO network
Two LEDs at the Ethernet ports to indicate the Link activity of the ports
OMRON
GRT1-PNT
FG
Gauge
20 AWG to 14 AWG
2
(0.5 to 2.0 mm
)
Section 2-1
2
).
Pin length: 8 to 10 mm
17