Input Shift (Correction) - Omron EJ1 User Manual

Modular temperature controllers
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Setting Input Specifications
Note
4-1-4

Input Shift (Correction)

Note
Variable type
E0/A0
Scaling Upper Limit
(See note.)
Scaling Lower Limit
Decimal Point Position (Channel) 0: **** (no decimal point)
Conditions for use
This parameter can be set only when operation is stopped.
Always set the Scaling Upper Limit > Scaling Lower Limit.
If the Scaling Lower Limit > Scaling Upper Limit, the larger value will function
as the Scaling Upper Limit.
Setting Example
In this example, scaling is set to display 0 to 5 V as 10.0% to 95.0%.
Scaling Upper Limit = 950
Scaling Lower Limit = 100
Decimal Point Position = 1
If there is a significant difference between the temperature at the measure-
ment point and the location where the temperature display is needed so that
the display/control performance is unsatisfactory at the present sensor posi-
tion (measurement point), the temperature difference can be set as an input
shift (correction) value.
Variable type
D5/95
Input Value 1 for Input Correction
Input Shift 1
Input Value 2 for Input Correction
Input Shift 2
Conditions for use
(1) The decimal point position is determined by the sensor selection.
(2) The decimal point position is determined by the sensor selection. In this
case, however, the 0 (****) decimal point position setting will be treated as
setting 1 (***.*).
Parameter name
(Channel)
(Channel)
The input type must be set to analog input.
Parameter name
(Channel)
(Channel)
(Channel)
(Channel)
No special conditions
Section 4-1
Setting range
Default
1999 to 9999
1000
1999 to 9999
0
1
1: ***.*
2: **.**
3: *.***
Setting range
Default
199.9 to 999.9 EU
0
(See note 1.)
199.9 to 999.9 EU
0.0
(See note 2.)
1999 to 9999 EU
1000
(See note 1.)
199.9 to 999.9 EU
0.0
(See note 2.)
53

Advertisement

Table of Contents
loading

Table of Contents