Omron EJ1 User Manual page 196

Modular temperature controllers
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Frame Configuration
BCC Calculation Example
Response Frame
End Codes
End code
Name
0F
FINS command error The specified FINS command could not be executed.
10
Parity error
11
Framing error
12
Overrun error
13
BCC error
14
Format error
16
Sub-address error
18
Frame length error
00
Normal completion
STX
02H 30H
BCC
=
:
XOR (exclusive OR) calculation
Note
No response will be returned unless the frame contains all elements up to the
ETX and BCC.
STX
Unit No.
02H
1
The OR of 1 bits in received data does not match the setting
for the communications parity.
Stop bit is 0.
The next data was received when the reception data buffer
was full.
The calculated BCC value is different from the received BCC
value.
The FINS-mini command text contains characters other than
0 to 9 and A to F. For details on the echoback test, refer to
6-4-10 Echoback Test.
SID and the FINS-mini command text are not included.
The sub-address is not included.
The received frame exceeds the specified number of bytes.
Command processing was completed normally.
■ End Code Example
When the Sub-address, SID, and FINS-mini Command Text Are Not Included
• Command
STX
Unit No.
02H
0
• Response
STX
Unit No.
02H
0
The sub-address is "00" and the end code is "16" (sub-address error).
Unit No.
Sub-address SID
30H
30H 30H 30H 30H
30H 30H 30H 30H 30H 30H
Text
Sub-address End code
0
0
2
2
2
BCC calculation range
Meaning
ETX
BCC
1
03H
Sub-address
End code
1
0
0
1
6
ETX BCC
FINS-mini command text
35H 30H 30H 03H 35H
35H
30H 30H
03H = 35H
ETX BCC
FINS-mini command text
03H
1
Error detection priority
8
2
1
3
5
7
6
4
None
ETX
BCC
03H
Section 6-2
1
171

Advertisement

Table of Contents
loading