Setting Control Specifications
MV
Inherits the MV that existed
before the mode change.
MV
changes
Manual
Auto
MV at Stop
This parameter sets the MV when control is stopped.
For heating/cooling control, the MV at Stop parameter applies to the cooling
side if the MV is negative and to the heating side if the MV is positive.
The default is 0.0, so an MV will not be output for either standard or heating/
cooling control with the default setting.
Variable type
Parameter name
D5/95
MV at Stop (Channel)
Conditions for use
No special conditions.
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
MV at PV Error
This parameter sets the MV when an input error or remote SP input error
occurs.
Variable type Parameter name
D5/95
MV at PV Error
(Channel)
Conditions for use
No special conditions.
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
MV Limiter
This function limits the MV output by applying upper and lower limits to the
calculated MV.
• The following MVs take priority over the MV limits.
• Manual MV
• MV at Stop
• MV at PV Error
Output
MV Upper Limit
MV Lower Limit
0%
Power
Power
MV
OFF
ON
changes
Power
interrupted
Setting range
5.0 to 105.0%
Setting range
5.0 to 105.0%
100%
Section 5-3
Time
Default
0
Default
0
75