Event Inputs (Tc2) - Omron EJ1G User Manual

Modular temperature controllers for gradient temperature control
Hide thumbs Also See for EJ1G:
Table of Contents

Advertisement

Other HFU Functions
5-7-2

Event Inputs (TC2)

Event Input
Assignment
Controlling Operation with
the Event Input's ON/OFF
Status
122
There are two event inputs in the TC2.
The following diagram shows the parameters that can be set in event input 1
or event input 2.
Some of the parameters are for all channels and others are for individual
channels.
EV1
Settable
parameters
All channels
Disabled
Bank (bit 0)
Bank (bit 1)
Stop (0)/Run (1)
Run (0)/Stop (1)
Auto (0)/Manual (1)
Variable type
F2/B2
Conditions for use
Note
This parameter can be set only when operation is stopped.
When this parameter has been changed, the new setting becomes effective
the next time a software reset is performed for the Unit or the next time power
is turned ON.
• Operation can be switched by OFF-to-ON or ON-to-OFF event-input tran-
sitions.
ON
OFF
Stop (0)/Run (1), Run (0)/Stop (1), Auto (0)/Manual (1)
Stop (0)/Run (1)
Run (0)/Stop (1)
Auto (0)/Manual (1)
EV2
EV3
EV2 to EV4 can be set in the same way.
Channel 3
Channel 2
Channel 1
Bank (bit 0)
Bank (bit 1)
Stop (0)/Run (1)
Run (0)/Stop (1)
Auto (0)/Manual (1)
Parameter name
Event Input 1 to 4 Assignment
(Common)
No special conditions.
Parameter
Section 5-7
EV4
Channel 64
Setting range
Default
0 to 69
0
Event input
Description
OFF
Stop
ON
Run
OFF
Run
ON
Stop
OFF
Auto
ON
Manual