Omron EJ1G User Manual page 165

Modular temperature controllers for gradient temperature control
Hide thumbs Also See for EJ1G:
Table of Contents

Advertisement

Detailed Description of Services
144
• When 100% AT Execute is specified during 40% AT Execute execution
• When 40% AT Execute is specified during 100% AT Execute execution
• When AT Execute/Cancel is specified for a GTC group
• Bank 0 Change to Bank 3 Change
Switches between banks 0 to 3. Refer to 5-7-1 Bank Function for details
on banks.
An operation error will occur if GT or autotuning is already being per-
formed for a specified channel.
• Reset Error
Clears the following errors: heater burnout latch, HS alarm latch, heater
overcurrent latch, heater overcurrent, and operation during error (selec-
tion D).
• Latch Cancel
Cancels alarm latches. This command is enabled when the alarm latch
function is used.
• Save RAM Data
Writes the settings for parameters that can be changed during operation
to EEPROM.
Time will be required and control performance may be affected if too
many parameters have been changed during operation. Save data to
RAM so that control performance will not be affected, e.g., save data
while operation is stopped.
• Parameter Initialization
Returns the current set values to their default values. The setting is not
saved to EEPROM, however, so Save RAM Data 2 should be executed if
required.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
After initializing the parameters, always cycle the power supply or perform
a software reset before starting control operations.
• Save RAM Data 2
Writes settings (except read-only settings) to EEPROM.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Register Unit Configuration (HFU)
Registers or resets the Basic Unit (TC4/2) configuration. Refer to Step 6
on page 39 under 3-1 Setup Procedure.
• Register Unit Configuration (TC4/2)
Registers or resets the G3ZA Unit Configuration. Refer to 4-5-1 Using
G3ZA Multi-channel Power Controllers for details on Unit configuration
registration.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Cancel Configuration Confirmation
If Units registered in the configuration cannot be detected, the configura-
tion confirmation status will not end. For example, if distributed placement
is used and the configuration has been registered, a no-power status will
be detected for the distributed Units. Use this operation command to can-
cel the configuration confirmation status. A configuration error will occur.
Note
Operation Commands for Switching Control Operation
An error may occur if Run/Stop, Auto/Manual, GT, Execute/Cancel, or AT Exe-
Section 6-4

Advertisement

Table of Contents
loading

Table of Contents