Setting Input Specifications
4-1-2

Temperature Inputs

4-1-3

Analog Inputs

Temperature Unit
Either °C or °F can be selected.
Variable type
E0/A0
Temperature Unit
Conditions for use The input type must be set to temperature input.
Cold Junction Compensation Method
Specifies whether cold-junction compensation is performed in the Tempera-
ture Controller or externally.
Enable external cold-junction compensation when using two thermocouples
to measure a temperature difference or using a external cold-junction com-
pensator for even greater precision.
Variable type
E0/A0
Cold Junction Compensation
Method
Conditions for use
The input type must be set to thermocouple or infrared temperature sensor.
When an analog input is selected, scaling can be performed as needed by the
control application.
• The Scaling Upper Limit, Scaling Lower Limit, and Decimal Point Position
parameters are used for scaling. These parameters cannot be used when
a temperature input type is selected.
• The Scaling Upper Limit parameter sets the physical quantity to be
expressed by the upper limit value of input, and the Scaling Lower Limit
parameter sets the physical quantity to be expressed by the lower-limit
value of input. The Decimal Point Position parameter specifies the num-
ber of digits below the decimal point.
• The following example shows scaling of an analog input (4 to 20 mA).
After scaling, the humidity can be read directly. In this case, the decimal
point is set for 1 digit below the decimal point.
Display
(humidity)
Upper limit (95.0%)
Lower limit (10.0%)
4
Parameter name
(Channel) 0: °C/1: °F
Parameter name
(Common)
Input (mA)
20
Section 4-1
Setting range
Default
0
Setting range
Default
0: External /
1
1: Internal
51