CHAPTER 4 APPLIED OPERATION
4.3 How to Use Event Input
J Input
assignments
Multi-SP function
0
1, 2
Run/Stop
Multi-SP
Auto/Manual
SP mode
4--8
• When using event input, mount the option unit (E53-AKB).
• Event inputs can be switched up to 100,000 times.
• You can choose from the following four event input functions:
Multi-SP
Run/Stop
Auto/Manual
SP mode
• In the case of the multi-SP function, the number of event inputs
(event input 1 or 2) set in the "multi-SP function" parameter (option
mode) are used.
• Other functions are assigned to event inputs 1 and 2 not used for the
multi-SP function according to the setting of the "event input assign-
ment 1 and 2" parameters (option mode). However, note that "event
input assignment 1/2" parameters cannot be used when only one unit of
the E53-AKB is installed.
Event input
1
0
1
2
• The following table shows the relationship between the settings and
functions of the "event input assignment 1 and 2" parameters.
Setting
Event input disabled
ON : Stop
ON : Manual
ON : RSP
2
Multi-SP
Other event input functions
Function
/OFF : Run
/OFF : Auto
/OFF : LSP