Omron CJ2 - 02-2010 User Manual page 611

Cj2 cpu unit software
Table of Contents

Advertisement

Address
Name
Words
Bits
A651
---
Program
Password
A654 to
---
Program File
657
Name
A720 to
---
Power ON
A722
Clock Data 1
A723 to
---
Power ON
A725
Clock Data 2
A726 to
---
Power ON
A728
Clock Data 3
CJ2 CPU Unit Software User's Manual
Function
Type in the password to replace a program.
A5A5 hex: Replacement Start Bit (A650.15) is enabled.
Any other value: Replacement Start Bit (A650.15) is dis-
abled.
When the power is turned ON or program replacement
is completed, the Replacement Start Bit will be turned
OFF, regardless of whether replacement was completed
normally or in error.
When program replacement starts, the program file
name will be stored in ASCII. File names can be speci-
fied up to eight characters in length excluding the exten-
sion.
File names are stored in the following order: A654 to
A657 (i.e., from the lowest word to the highest), and
from the highest byte to the lowest. If a file name is less
than eight characters, the lowest remaining bytes and
the highest remaining word will be filled with spaces (20
hex). Null characters and space characters cannot be
used within file names.
Example: File name is ABC.OBJ
These words contain the same time data as the startup
time stored in words A510 to A511, as well as the month
and year information.
A720.00 to A720.07: Seconds (00 to 59)
A720.08 to A720.15: Minutes (00 to 59)
A721.00 to A721.07: Hour (00 to 23)
A721.08 to A721.15: Day of month (01 to 31)
A722.00 to A722.07: Month (01 to 12)
A722.08 to A722.15: Year (00 to 99)
These words contain the time at which the power was
turned ON one time before the startup time stored in
words A510 and A511.
A723.00 to A723.07: Seconds (00 to 59)
A723.08 to A723.15: Minutes (00 to 59)
A724.00 to A724.07: Hour (00 to 23)
A724.08 to A724.15: Day of month (01 to 31)
A725.00 to A725.07: Month (01 to 12)
A725.08 to A725.15: Year (00 to 99)
These words contain the time at which the power was
turned ON two times before the startup time stored in
words A510 and A511.
A726.00 to A726.07: Seconds (00 to 59)
A726.08 to A726.15: Minutes (00 to 59)
A727.00 to A727.07: Hour (00 to 23)
A727.08 to A727.15: Day of month (01 to 31)
A728.00 to A728.07: Month (01 to 12)
A728.08 to A728.15: Year (00 to 99)
Status
after
Status at
Settings
mode
startup
change
---
Retained
Cleared
---
Retained
Cleared
See Function col-
Retained
Retained
umn.
See Function col-
Retained
Retained
umn.
See Function col-
Retained
Retained
umn.
Appendices
Write timing/
Related flags,
settings
---
---
Written when
power is
turned ON.
Written when
power is
turned ON.
Written when
power is
turned ON.
A-135